Daikin VAM Series Engineering Data page 102

Heat reclaim ventilator
Table of Contents

Advertisement

Sound Level
VAM650HVE / VAM650HVLT
Hz
Model Power Supply
63
Notch
U-H
51.3 48.4 39.1 31.5 31.4 26.2 20.8 17.8
220 V
H
50.3 47.0 37.2 30.5 29.6 25.0 19.8 17.1
L
48.6 45.9 34.5 28.5 27.6 22.5 18.1 15.9
U-H
51.8 48.9 39.6 32.0 31.9 26.7 21.3 18.3
VAM
650
50 Hz
230 V
H
50.8 47.5 37.7 31.0 30.1 25.5 20.3 17.6
HVE
L
49.1 46.4 35.0 29.0 28.1 23.0 18.6 16.4
U-H
51.8 48.9 39.6 32.0 31.9 26.7 21.3 18.3
240 V
H
50.8 47.5 37.7 31.0 30.1 25.5 20.3 17.6
L
49.6 46.9 35.5 29.5 28.6 23.5 19.1 16.9
U-H
48.3 47.7 39.2 32.5 32.4 26.8 21.2 18.8
VAM650
HVE/
60 Hz 220 V
H
49.9 47.1 38.1 31.8 31.1 26.2 20.6 18.4
HVLT
L
46.5 42.7 32.5 26.9 27.2 20.8 17.1 14.7
VAM1000HVE / VAM1000HVLT
Hz
Model Power Supply
63
Notch
U-H
53.7 53.2 44.4 37.6 32.8 29.5 22.5 17.4
220 V
H
52.4 51.6 42.2 35.3 30.6 27.4 20.6 16.8
L
51.3 48.9 39.4 34.3 28.9 24.8 18.7 17.1
U-H
54.2 53.7 44.9 38.1 33.3 30.0 23.0 17.9
VAM
1000
50 Hz
230 V
H
52.9 52.1 42.7 35.8 31.1 27.9 21.1 17.3
HVE
L
52.3 49.9 40.4 35.3 29.9 25.8 19.7 18.1
U-H
54.7 54.2 45.4 38.6 33.8 30.5 23.5 18.4
240 V
H
53.4 52.6 43.2 36.3 31.6 28.4 21.6 17.8
L
52.8 50.4 40.9 35.8 30.4 26.3 20.2 18.6
U-H
54.0 53.8 44.8 37.6 33.4 30.1 23.0 18.1
VAM1000
HVE/
60 Hz 220 V
H
50.8 49.7 40.0 33.1 28.6 25.4 18.7 14.8
HVLT
L
47.1 45.2 35.5 31.3 25.6 21.2 15.2 13.5
VAM2000HVE / VAM2000HVLT
Hz
Model Power Supply
63
Notch
U-H
62.5 57.5 43.0 37.4 34.3 28.9 23.6 18.3
220 V
H
60.7 55.6 40.4 35.3 32.4 26.8 20.9 17.2
L
58.6 53.4 37.4 32.8 28.8 24.1 19.5 16.5
U-H
63.0 58.0 43.5 37.9 34.8 29.4 24.1 18.8
VAM
2000
50 Hz
230 V
H
61.7 56.6 41.4 36.3 33.4 27.8 21.9 18.2
HVE
L
60.1 54.9 38.9 34.3 30.3 25.6 21.0 18.0
U-H
63.0 58.0 43.5 37.9 34.8 29.4 24.1 18.8
240 V
H
62.2 57.1 41.9 36.8 33.9 28.3 22.4 18.7
L
60.6 55.4 39.4 34.8 30.8 26.1 21.5 18.5
U-H
63.1 58.6 44.1 38.5 35.5 30.1 24.8 19.3
VAM2000
HVE/
60 Hz 220 V
H
59.1 54.0 38.8 33.6 31.5 25.2 19.3 15.6
HVLT
L
56.4 50.6 35.1 30.1 26.4 21.5 16.2 13.8
Measuring place
Notes:
1. Operation sound is measured in an anechoic chamber.
2. The sound is measured at 1.5 m below the center of the body.
3. The operating sound level may become greater than this value depending on
the operating conditions, reflected sound, and peripheral noise.
4. Operation sound differs with operation and ambient conditions.
5. U-H: Ultra high
H: High
L: Low
100
125
250
500
1000 2000 4000 8000
125
250
500
1000 2000 4000 8000
125
250
500
1000 2000 4000 8000
dB(A)
VAM800HVE / VAM800HVLT
Model Power Supply
Notch
U-H
220 V
H
L
U-H
VAM
800
50 Hz
230 V
H
HVE
L
U-H
240 V
H
L
U-H
VAM800
HVE/
60 Hz 220 V
H
HVLT
L
VAM1500HVE / VAM1500HVLT
dB(A)
Model Power Supply
Notch
U-H
220 V
H
L
U-H
VAM
1500
50 Hz
230 V
H
HVE
L
U-H
240 V
H
L
U-H
VAM1500
HVE/
60 Hz 220 V
H
HVLT
L
dB(A)
EDMMT712101
Hz
63
125
250
500
1000 2000 4000 8000
53.0 52.7 44.2 37.2 31.9 28.5 21.7 17.1
52.0 50.5 42.2 35.2 30.4 26.6 19.9 17.0
48.4 46.9 37.4 32.7 27.2 22.3 16.8 16.1
53.5 53.2 44.7 37.7 32.4 29.0 22.2 17.6
53.0 51.5 43.2 36.2 31.4 27.6 20.9 18.0
50.4 48.9 39.4 34.7 29.2 24.3 18.8 18.1
54.0 53.7 45.2 38.2 32.9 29.5 22.7 18.1
53.5 52.0 43.7 36.7 31.9 28.1 21.4 18.5
50.9 49.4 39.9 35.2 29.7 24.8 19.3 18.6
53.4 52.0 43.6 36.8 31.5 28.4 21.5 16.7
50.4 48.0 39.3 32.7 27.9 24.1 17.3 14.7
47.8 43.7 34.9 29.2 23.9 20.0 14.1 13.9
Hz
63
125
250
500
1000 2000 4000 8000
61.5 57.1 42.8 37.1 33.2 28.7 23.3 17.9
59.9 55.2 39.9 34.7 32.3 26.2 20.4 16.2
57.5 52.4 36.6 31.6 28.0 23.2 17.7 14.8
62.0 57.6 43.3 37.6 33.7 29.2 23.8 18.4
60.9 56.2 40.9 35.7 33.3 27.2 21.4 17.2
59.5 54.4 38.6 33.6 30.0 25.2 19.7 16.8
62.5 58.1 43.8 38.1 34.2 29.7 24.3 18.9
61.4 56.7 41.4 36.2 33.8 27.7 21.9 17.7
60.0 54.9 39.1 34.1 30.5 25.7 20.2 17.3
62.3 58.2 43.8 37.9 34.7 29.6 23.6 18.4
58.6 53.0 37.6 32.9 29.7 24.4 18.5 15.7
54.9 49.4 33.0 28.5 24.8 20.0 14.0 12.9
Location of microphone
Measuring point
VAM-HVE/HVLT Series
dB(A)
dB(A)
1.5 m
3D132659

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents