Daikin VAM Series Engineering Data page 38

Heat reclaim ventilator
Table of Contents

Advertisement

Control System
Zone management [Central remote controller (DCS302CA61)]
Purpose • Function
  Up to 64 groups of Heat Reclaim Ventilator Unit and indoor units can be connected to make individual/batch start/stop available on
a zone basis together with various monitoring.
※Energy-saving interlocking control and independent ventilation operation is possible within the same zone.
※Ventilation mode and ventilation rate can be switched using DCS302CA61.
POINT
  Group number needs to be set for centralized control.
  Heat Reclaim Ventilator Unit to be interlocked with air conditioners should be assigned to the same zone as the air conditioners.
In this case, zone interlock setting needs to be made on the Heat Reclaim Ventilator Unit.
  ON/OFF operation cannot be performed from the remote controller for Heat Reclaim Ventilator Unit in Zone 1 (settings other than
ON/OFF can be made).
  Zone interlock setting is not required for Zone 2. This means that the factory default settings are maintained.
  When operation is performed without remote controller, the unit can be operated only from central remote controller.
Example of control wiring
Switch number that needs to be changed for the system
Field settings using remote controller is required.
Field settings using remote controller
  In case of Zone 1 ...... "Yes" [17(27)•8•02]
  In case of Zone 2 ...... Factory default setting (no setting is required)
Centralized zone interlock setting
Factory default setting
Essential optional accessory
  Remote controller (only if connected)
BRC1H62•BRC1E63
36
Power supply
P1P2
Indoor unit
P1P2
Remote controller
P1P2
Heat Reclaim
Ventilator Unit
P1P2
Remote controller
Note) The maximum length of centralized transmission line (between F1 and F2) is up to 1000m.
Mode
Setting switch
No.
No.
17 (27)
8
Central remote
controller
F1 F2
F1 F2
P1P2
Heat Reclaim
Ventilator Unit
P1P2
Remote controller
F1 F2
F1 F2
P1P2
Heat Reclaim
Ventilator Unit
\
P1P2
Remote controller
Setting position
01
02
No
Yes
EDMMT712101
VAM-HVE/HVLT Series