Daikin VAM Series Engineering Data page 33

Heat reclaim ventilator
Table of Contents

Advertisement

EDMMT712101
Control by 2 remote controllers
Purpose • Function
  One unit (or one group) of Heat Reclaim Ventilator Unit
Perform fine operation of Heat Reclaim Ventilator Unit and display output, at hand or at a distance, by using two remote controllers.
  All operating and display functions of the remote controller can be performed from either one of the remote controllers. (However,
field settings can be made only by using the main remote controller)
POINT
  Wiring to the remote controllers is branched out from the main unit (as shown in the illustration).
(The wiring can be routed from the main remote controller to the sub remote controller. However, it takes a lot of work to put two
wires inside the remote controller.)
  Different types of remote controller (BRC1H62, BRC1E63) cannot be mixed for use.
Example of control wiring
P1P2
P1P2
P1P2
(Main)
(Sub)
Remote
Remote
controller
controller
Group control
Purpose • Function
  Controls multiple Heat Reclaim Ventilator Units (up to 16 units) simultaneously on a large floor.
  All operations and individual setting functions of the remote controller can be collectively performed.
  Even in the event where unusual display is shown, you can identify specifically which Heat Reclaim Ventilator Unit output the signal
by confirming the unit number.
(Control by 2 remote controllers can be performed if one more remote controller is connected.)
POINT
  Address is automatically assigned and thus no address setting is required.
(Addresses are assigned arbitrarily. To check the address number, use the service mode setting "forced fan ON" and check the
operation status.)
  At least one remote controller is always required.
Example of control wiring
P1 P2
Heat Reclaim
Ventilator Unit
Remote
P1 P2
controller
VAM-HVE/HVLT Series
Heat Reclaim
Ventilator Unit
Note) The maximum length of remote
controller cord is up to 500m.
▪▪▪
P1 P2
Heat Reclaim
Ventilator Unit
Note) The maximum length of remote controller cord is up to 500m.
Switch number that needs to be changed for the
system
Set one of the remote controllers to be the sub remote controller.
Essential optional accessory
  Remote controller × 2
BRC1H62•BRC1E63
Switch number that needs to be
changed for the system
NIL. (Remans at the factory default settings)
Essential optional accessory
P1 P2
  Remote controller
Heat Reclaim
BRC1H62•BRC1E63
Ventilator Unit
Control System
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents