Daikin VAM Series Engineering Data page 44

Heat reclaim ventilator
Table of Contents

Advertisement

Control System
Selection of External Input Terminal Function
Purpose • Functions
Switches functions by contact signal input to (J1, JC) terminals.
POINT
Fresh-up
ON/OFF and changeover of fresh-up
.........................
(Pre Vent)
operation mode can be done. (See page
41 for more details)
Batch alarm
It is possible to display the error code "60"
...................
on the remote controller. Fan operation
continues.
Batch error
It is possible to display the error code "60"
......................
on the remote controller. Fan operation
stops.
Forced OFF
Operation stops.
.....................
Fan forced stop
The fan stops while the unit is in operation.
............
Airflow rate increase
The ventilation airflow is switched from
....
"Low" to "Ultra high" or "High".
 
Setting
Field setting for
by remote
ventilation fan
controller
Normal mode
Low
Ultra high mode
Normal mode
High
Ultra high mode
Example of control wiring
Transmission wiring is up to 50m.
J1
JC
F1 F2
P1 P2
Heat Reclaim Ventilator Unit
Remote controller
P1 P2
Switch number that needs to be changed for the system
Field settings using remote controller is required.
Field settings using remote controller  
Selection of External Input
Terminal Function
Field setting for ventilation fan
Essential optional accessory
NIL.
42
Remote
Fan notch with external input
controller
Open
Short circuit
display
Low
High
Low
Low
Ultra high
High
High
High
Ultra high
Ultra high
(Contact on site)
Setting
Mode
switch
No.
01
No.
Fresh-up
18 (28)
8
(Pre Vent)
17 (27)
4
Normal
Reset
Input
Functions
Position
contact
01
Fresh-up
a
02
Batch alarm
a
03
Batch error
a
04
Forced OFF
b
Fan forced
05
b
OFF
06
More airflow
a
Specifications for external contact
• Non-voltage normally open contact or non-voltage normally closed contact
• Microcurrent contact (Minimum applicable load: DC12V, 1mA or below)
Setting position
02
03
Batch alarm
Batch error
Forced OFF
Ultra high
EDMMT712101
Fan
Operation
Behaviors
operation
lamp
Fresh-up operation
Operation
ON
Displays error code
Operation
ON
"60"
Displays error code
Stop
Blinking
"60"
No automatic
Stop
OFF
recovery
Performs automatic
Stop
ON
recovery
Airflow rate increases
(Low → High/Ultra
Operation
ON
high)
 Factory default setting
04
05
06
Fan forced
More airflow
OFF
VAM-HVE/HVLT Series