Set Under-Voltage Protection (Uvp) - ITech IT6000D Series User Manual

High power programmable dc power supply
Hide thumbs Also See for IT6000D Series:
Table of Contents

Advertisement

4. Set the warm-up time Warm-up, protection limit Level and delay time Delay

4.5.5 Set Under-Voltage Protection (UVP)

Users can enable the UVP function and set the instrument warm-up time
Warm-up, protection limit Level and protection delay time Delay. When the
voltage (i.e., the Meter value) is lower than this protection limit and the warm-up
time, delay time are exceeded, the power supply will enter the UVP state.
Possible Cause
Many reasons can cause UVP, the details are as follows:
How to Set
The operation steps to set UVP are as follows.
1. Press the composite keys [Shift]+[Recall] (Protect) on the front panel to en-
2. Press the up/down key or rotate the knob to select 5. UVP (Off) and press
3. Press the left/right key or rotate the knob to select On and press [Enter] to
4. Set the warm-up time Warm-up, protection limit Level and delay time Delay
in sequence, and then press [Enter] to confirm.
The VFD screen returns to the Protect menu and the UCP setting (take 10S,
0.1A, 1S as an example) is displayed as follows:
PROTECT
4.UCP
10S,
0.1A, 1.000S
The set protection limit Level is greater than the voltage Meter value.
The external (AC input) inputs a lower voltage.
The power supply outputs a low voltage due to a fault.
ter the protection menu.
[Enter].
enter the setting interface.
in sequence, and then press [Enter] to confirm.
The VFD screen returns to the Protect menu and the UVP setting (take 10S,
1V, 1S as an example) is displayed as follows:
PROTECT
5.UVP
10S,
1V, 1.000S
Copyright © Itech Electronic Co., Ltd.
Power Supply Function
64