It6010D-80-300 - ITech IT6000D Series User Manual

High power programmable dc power supply
Hide thumbs Also See for IT6000D Series:
Table of Contents

Advertisement

Note: 1. Models without emergency stop module (i.e. AC contactor not in-
cluded), other AC input voltage ranges are required for customization. Models
without emergency stop module and assembled to the cabinet, with AC input
voltage in the range of 198~264V, need to be customized while derating by
50%. Models with emergency stop module (including AC contactor) only sup-
port 380VAC±10% for standard AC input voltage, 480VAC±10% voltage is re-
quired for customization.

6.1.1.2 IT6010D-80-300

Rated value
( 0 ℃-50 ℃)
Line Regulation
±(%of Output+Offset)
Load Regulation
±(%of Output+Offset)
Setup Resolution
Read Back Resolution
Setup Accuracy
( within 12 months, 25℃
±5℃)
±(%of Output+Offset)
Read Back Accuracy
( within 12 months, 25℃
±5℃)
±(%of Output+Offset)
Ripple
(20Hz -20MHz)
Setup Temperature
Coefficient
Parameter
Output Voltage
Output Current
Output Power
Voltage
Current
Voltage
Current
Voltage
Current
Power
Voltage
Current
Power
Voltage
Current
Power
Voltage
Current
Power
Voltage
Current
Voltage
Copyright © Itech Electronic Co., Ltd.
Technical Specification
IT6010D-80-300
0~80V
0~300A
0~10kW
≤0.01%FS
≤0.05%FS
≤0.02%FS
≤0.05%FS
0.001V
0.01A
0.001kW
0.001V
0.01A
0.001kW
≤0.02% + 0.02%FS
≤0.1% + 0.1%FS
≤0.5% + 0.5%FS
≤0.02% + 0.02%FS
≤0.1% + 0.1%FS
≤0.5% + 0.5%FS
≤120mVpp(MAX: ≤300mVpp)
≤0.1%FS RMS
≤50PPM/℃
128

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IT6000D Series and is the answer not in the manual?

Questions and answers

Table of Contents