Error Messages On Optional Remote Display - Xantrex BC3012 User Manual

Table of Contents

Advertisement

Troubleshooting

Error Messages on Optional Remote Display

Table 3-2 Error Messages
Onboard Status Panel
Display
Indicator lights
Red fault indicator light
E R R
flashing or illuminated
A C L
Red fault indicator light
E r r
illuminated
b a t
P o L
Red fault indicator light
E r r
flashing
C H f
C H g
H o t
Red fault indicator light
E r r
illuminated
C H g
H o t
Green 10% indicator light
C L d
flashes
Green bank indicator light for
affected battery bank
illuminated
3–4
Fault
Solution
Fault
A fault has been detected. The fault code
will be shown immediately after
AC Low
Check AC connections, check AC
Warning
availability at source.
Reverse
Reverse Polarity Battery connected.
Polarity
Check connections. Ensure correct
polarity (negative connected to negative,
positive connected to positive).
Charger
Call for service.
Hardware
Fault
Over-
Allow the BC Series to cool. Improve
temperature
ventilation or install in cooler location. If
Warning
the temperature increases, the BC Series
will enter the fault level and stop
functioning.
Over-
Allow the BC Series to cool. Improve
temperature
ventilation or install in cooler location.
Shutdown
Battery Too
Allow batteries to warm up before
Cold Warning
attempting to charge again. Charging a
battery that has frozen is a potential
explosion hazard. If the temperature
drops, the BC Series will enter the fault
level and stop charging the affected bank.
.
E r r
975-0188-01-01

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bc5012Bc1524Bc2524

Table of Contents