Table 3-2 Error Messages
Onboard Status Panel
Display
Indicator lights
Red fault indicator light
E r r
illuminated
C L d
Green 10% indicator light
flashes
Green bank indicator light for
affected battery bank
illuminated
25% current indicator light
D I S
flashes
Green bank indicator light for
H I
the affected battery bank
illuminated
Red fault indicator light
E r r
illuminated
H I
Green bank indicator light for
the affected battery bank
illuminated
975-0188-01-01
Error Messages on Optional Remote Display
Fault
Solution
Battery Too
Allow batteries to warm up before
Cold
attempting to charge again. Charging a
Shutdown
battery that has frozen is a potential
explosion hazard.
Battery
Wait 15 minutes for the next battery
Disqualified
detection cycle. The warning may be
Warning
temporary.
Verify that the battery meets the minimum
AmpHour rating (BC1524: 30 Ah,
BC2524: 50 Ah, BC3012: 60 Ah,
BC5012: 100 Ah)
Try adding a small DC load.
Replace the battery.
Over Voltage
Check battery. Do not charge a battery
Shutdown
rated at more than 12 volts nominal
Warning
(BC3012, BC5012) or 24 volts nominal
(BC1524, BC2524).
Disconnect or turn off other charging
sources such as the alternator or the
charger on a generator with electric start.
If the warning level escalates without
being corrected, the BC Series enter the
fault level and stop charging the affected
bank.
Over Voltage
Check battery. Do not charge a battery
Shutdown
rated at more than 12 volts nominal
(BC3012, BC5012) or 24 volts nominal
(BC1524, BC2524).
Disconnect or turn off other charging
sources such as the alternator or the
charger on a generator with electric start.
3–5