Float voltage (in VDC for BC3012
and BC5012)
(Multiply VDC by 2 to get the
float voltage for BC1524 and
BC2524)
Equalize mode current
Equalize mode—maximum output
voltage
Off-state current draw (with
remote installed)

AC Input Specifications

AC input voltage range
Maximum AC input current
Power factor at rated load
Frequency
Efficiency – peak
Surge protection
975-0188-01-01
50 °C (122 °F)
Flooded
12.8
Gel
13.1
AGM
12.9
Lead-calcium 12.8
50% rated output
BC3012:
16.0 VDC
BC5012:
16.0 VDC
BC1524:
32.0 VDC
BC2524:
32.0 VDC
BC3012:
<20 mA
BC5012:
<20 mA
BC1524:
<15 mA
BC2524:
<15 mA
100 – 260 VAC at full power
90 – 105 VAC at 80% restricted load
Note: Charger may not start with input voltage
<100 VAC
at 100 VAC
BC3012:
6 AAC
BC5012:
10 AAC
BC1524:
6 AAC
BC2524:
10 AAC
≥0.95
47 – 63 Hz
12 V units: 80% @ 120 VAC, 83% @ 230 VAC
24 V units: 85% @ 120 VAC, 87% @ 230 VAC
Line-to-neutral surge protector rated at 275 VAC
AC Input Specifications
<0 °C (32 °F)
25 °C (77 °F)
13.5
14.2
13.8
14.5
13.4
13.9
13.5
14.2
at 184 VAC
BC3012:
4.3 AAC
BC5012:
5.7 AAC
BC1524:
4.3 AAC
BC2524:
5.7 AAC