Troubleshooting
Table 3-2 Error Messages
Onboard Status Panel
Display
Indicator lights
Green 100% indicator light
H o t
flashes
Green bank indicator light for
the affected battery bank
illuminated
Red fault indicator light
E r r
illuminated
H o t
Green 100% indicator light
flashes
Green bank indicator light for
affected battery bank
illuminated
n o
Red fault indicator light
E r r
illuminated
n o
B a t
3–6
Fault
Solution
Battery too
Allow battery to cool. Improve ventilation
Hot Warning
or install in cooler location. It may
indicate a shorted cell in the battery or
excessive water loss. If the temperature
increases, the BC Series will enter the
fault level and stop charging the affected
bank.
Battery too
Allow battery to cool. Improve ventilation
Hot Shutdown
or install in cooler location. It may
indicate a shorted cell in the battery or
excessive water loss.
Cannot apply
The operation you have tried to execute
change
cannot be completed.
No batteries
The charger did not detect any batteries.
detected
975-0188-01-01