The BC Series is designed to work with a minimum battery bank size. Each bank
should meet the minimum Ah rating shown in Table 1-1.
Table 1-1 Minimum Battery Bank Size
Minimum Battery
Bank Size (Ah)

Battery Temperature Sensors

Xantrex strongly recommends that you install a Battery Temperature Sensor (BTS)
to protect your battery and improve charging accuracy. It is best to use a separate
BTS with each individual battery bank, to provide optimal charging and protection
of each bank. If no BTS is connected, the charger defaults to the charging
conditions for 40 °C (104 °F). At this temperature the charging voltage is lower to
keep batteries from overcharging; charging will be slower and the batteries will be
slightly undercharged.
One BTS is provided with your BC Series, and additional battery temperature
sensors may be purchased separately.
1–8
BC 1524
BC 2524
30
50
BC 3012
BC 5012
60
100