Connecting Power to Cisco ASR 1002 Router
Only trained and qualified personnel should be allowed to install, replace, or service this equipment.
Warning
Statement 1030
This section provides the procedures for connecting AC-input and DC-input power to your
Cisco ASR 1002 Router.
The DC power supply for the Cisco ASR 1006, ASR 1004, and ASR 1002 routers operate at individual
specifications.
Table 6-6
Cisco ASR 1000
Series Router DC
Power Supply
System Input Rating (Amps)
Cisco ASR 1006
40
Cisco ASR 1004
24
Cisco ASR 1002
16
For example, the Cisco ASR 1002 Router DC power supply, with 16 Amp input rating must use an AWG #12 gauge wire for a 20Amp circuit breaker and
an AWG #10 gauge wire for a 30Amp circuit breaker.
All Cisco ASR 1000 Series Router AC power supplies require a 20 AMP circuit breaker.
Note
Detailed instructions for removing and replacing the Cisco ASR1002 Router AC and DC power supplies
Note
are in
Read the safety warnings before you begin.
Never install an AC power module and a DC power module in the same chassis. Statement 1050
Warning
Warning
Installation of the equipment must comply with local and national electrical codes. Statement 1074
Warning
When installing or replacing the unit, the ground connection must always be made first and
disconnected last. Statement 1046
Warning
This equipment must be grounded. Never defeat the ground conductor or operate the equipment in the
absence of a suitably installed ground conductor. Contact the appropriate electrical inspection
authority or an electrician if you are uncertain that suitable grounding is available. Statement 1024
Cisco ASR 1000 Series Aggregation Services Routers Hardware Installation and Initial Configuration Guide
6-28
Table 6-6
shows the common input ranges and circuit breaker requirements.
Cisco ASR 1000 Series Router DC Power Supply System Input Requirements
Removing and Replacing a Cisco ASR 1002 Router Power Supply, page
Chapter 6
Circuit Breaker Amps
Minimum
Maximum
Always 50
30
40
20
30
Cisco ASR 1002 Router Overview and Installation
AWG # Wire
Minimum
Maximum
Always AWG #6 wire
10
8
12
10
8-40.