SECTIOn 3 |
ii. Table 3.2.2 is for EVO-3012E and is based on the AC Input Current Limit
("GrID MAX CUrrENT" and"GEN MAX CUrrENT") set at 25A which is its full
rated AC input current requirement and is equal to the sum of the full rated AC
side charging current of 12A ( for full rated DC side charging current of 130A)
and full rated AC pass through current of 13A (equal to the full rated AC
output current of 13A in Inverting Mode)
iii. Table 3.2.3 is for EVO-4024E and is based on the AC Input Current Limit
("GrID MAX CUrrENT" and"GEN MAX CUrrENT") set at 36A which is its full
rated AC input current requirement and is equal to the sum of the full rated AC
side charging current of 18A ( for full rated DC side charging current of 110A)
and full rated AC pass through current of 18A (equal to the full rated AC
output current of 18A in Inverting Mode)
5) Column 6 indicates the Amp rating of EXTErNAL breaker that is required to be
installed in the Consumer Unit / Load Center / breaker Panel feeding the unit. The
Amp rating of this breaker is based on the following considerations:
a. Not less than the programmed value of the AC Input Current Limit ("GrID
MAX CUrrENT" and"GEN MAX CUrrENT" at Column 5)
b. Type of breaker: Standard Moulded Case Circuit breaker (MCCb) for 230VAC,
50Hz Consumer Unit / Load Center / breaker Panel
6) Column 7 indicates conductor size based on the following guidelines:
a. british Standard bS 7671 : 2008 - requirements for Electrical Installations:
(i)
Table 4D2A for multi-core, 70°C copper conductor cable
(ii) Ambient temperature of 30°C
(iii) reference method "b"- enclosed in conduit on a wall or in trunking, etc.
(iv) 1 two-core cable with Protective Earth (PE) conductor
(v) Conductor temperature rating has been taken as 70°C to meet 70°C
maximum temperature of MCCb terminals as per bS EN-60947-2
b. Current carrying capacity = the MCCb rating at Column 6
3.9 SiZing oF wiring AnD breAkerS - AC outPut SiDe
wArning!
AC breakers for the AC output circuits have NOT been provided internally. These have to be
provided externally by the installer / user based on guidelines given below. Please note that
guidelines given below on wire sizing and over-current protection will be superseded by the
applicable National / Local Electrical Codes.
Attention!
Breakers AC pour les circuits d'entrée AC ont pas été fournis en interne. Ceux-ci doivent être fournies à l'extérieur par
l'installateur / utilisateur sur la base des directives données ci-dessous. Se il vous plaît noter que les directives ci-dessous
sur dimensionnement des câbles et protection contre les surintensités seront remplacées par les nationaux / codes
électriques locaux applicables.
46 | SAMLEX AMErICA INC.