SECtION 4 |
Gen MAX CURRent:
Up Key
SELECT GROUP
CHARGE CURVE
HiGH CUt oFF:
If the AC input frequency is over the value of "HIGH CUT OFF" when in "Charging Mode",
the EVO
Inverter/Charger will transfer to Inverting Mode.
TM
Up Key
SELECT GROUP
CHARGE CURVE
HiGH ReSet:
This is the reset frequency at which the unit will revert to "Charging Mode" after it has
switched over to "Inverter Mode" due to input frequency rising above "HIGH CUT OFF".
Up Key
SELECT GROUP
CHARGE CURVE
LoW CUt oFF:
If the AC input frequency is below "LOW CUT OFF" value when in "Charging Mode", the
EVO
Inverter/Charger will transfer to Inverting Mode.
TM
Up Key
SELECT GROUP
CHARGE CURVE
LoW ReSet:
This is the reset frequency at which the unit will revert to "Charging Mode" after it has
switched over to "Inverting Mode" due to input frequency falling below "LOW CUT OFF".
Up Key
SELECT GROUP
CHARGE CURVE
4.6 GRoUP 3 PARAMeteR Set UP: inPUt LoW LiMit
Please refer to Parameters under Group 3 at Fig 4.1. Details of Parameter set up are given below:
tABLe 4.6. GRoUP 3 PARAMeteR Set UP: inPUt LoW LiMit
Screen
no. for
Group
Parameter
3 (Fig
4.1)
1
ReSet VoLtAGe
2
CUt oFF VoLt 1
3
DeteCt tiMe 1
4
CUt oFF VoLt 2
5
DeteCt tiMe 2
6
CUt oFF VoLt 3
7
DeteCt tiMe 3
28 | SAMLEX AMERICA INC.
Parameter Setup
Enter Key
SELECT GROUP
DEFAUT FREQ
INPUT SETTING
0= 50Hz
Enter Key
SELECT GROUP
DEFAUT FREQ
INPUT SETTING
0= 50 Hz
Enter Key
SELECT GROUP
DEFAUT FREQ
INPUT SETTING
0= 50 Hz
Enter Key
SELECT GROUP
DEFAUT FREQ
INPUT SETTING
0= 50 Hz
Enter Key
SELECT GROUP
DEFAUT FREQ
INPUT SETTING
0= 50 Hz
eVo-
2212e
Up Key x 2
GEN MAX CURRENT
16.00 A
Up Key x 3
HIGH CUT OFF
55.00 Hz
Up Key x 4
HIGH RESET
54.00 Hz
Up Key x 5
LOW CUT OFF
45.00 Hz
Up Key x 6
LOW RESET
46.00 Hz
Setting range
eVo-
eVo-
eVo-
3012e
2224e
4024e
140.0 – 200.0V
140.0 – 200.0V
0 – 2000 cycles
140.0 – 200.0V
0 – 2000 cycles
140.0 – 200.0V
0 – 2000 cycles
APPENDIX A
Enter Key
KEY IN PASSWORD
0000
Password 8052
See Section 4.3.1
Enter Key
KEY IN PASSWORD
0000
Password 8052
See Section 4.3.1
Enter Key
KEY IN PASSWORD
0000
Password 8052
See Section 4.3.1
Enter Key
KEY IN PASSWORD
0000
Password 8052
See Section 4.3.1
Enter Key
KEY IN PASSWORD
0000
Password 8052
See Section 4.3.1
Default value
eVo-
eVo-
2212e
3012e
190.0V
180.0V
300 cycles
170.0V
60 cycles
160.0V
1 cycle
GEN MAX CURRENT
16.00 A
HIGH CUT OFF
55.00 Hz
HIGH RESET
54.00 Hz
LOW CUT OFF
45.00 Hz
LOW RESET
46.00 Hz
eVo-
eVo-
2224e
4024e