SECtION 4 |
4= Generator 2
This Function will start the Generator at "LOW VOLT ALARM" and stop the Generator after the
desired programmed value of run time of the Generator = "GEN ON TIME" (0-240 min; Default
= 60 min) counted from the time the Status Relay is switched ON (energized)
• I f the battery voltage drops to "LOW VOLT ALARM" [(i) for 12V: 9.5V – 12.5V / Default
11.0V (ii) for 24V: 19.0V – 25.0V / Default 22.0V] or lower for continuous period =
"GS DETECT TIME" (0-600 sec; Default 10 sec), the Status Relay will be switched ON
(energized). "Common" and "NO" contacts of the Status Relay will close to initiate
automatic starting of the Generator
• O nce the generator has started and starts feeding AC output (within the programmed
limits of voltage and frequency), the EVO
"Charging Mode". Battery charging will be initiated as per full and complete 3-Stage
Charging Algorithm ("CHARGE MODE" 0=Normal).
• T he Status Relay will be switched OFF (de-energized) after expiry of the desired
programmed Generator run time = "GEN ON TIME" (0-240 min; Default = 60 min)
counted from the time the Status Relay is switched ON (energized). "Common" and
"NO" contacts of the Status Relay will open to initiate automatic stopping of the
Generator. When AC output from the Generator switches OFF, EVO
"Inverting Mode" (NOTE: The State of Charge of the battery after the Status Relay has
been switched OFF (de-energized) and Generator is stopped will be indeterminate).
Diagram showing steps for programming the above RELAY FUNCTION is given below:
Up Key x 4
SELECT GROUP
CHARGE CURVE
CoMM iD:
Communication ID- This sets the ID number for the COMM Port and EVO-RC Remote Control.
Up Key x 4
SELECT GROUP
CHARGE CURVE
BUZZeR:
Set the buzzer ON/OFF.
Up Key x 4
SELECT GROUP
CHARGE CURVE
DiSCHARGe BeeP:
To select the buzzer ON/OFF while in "Inverting Mode".
Up Key x 4
SELECT GROUP
CHARGE CURVE
DeFAULt ReSet
This is to reset all of the parameters to the Default Values.
Up Key x 4
SELECT GROUP
CHARGE CURVE
36 | SAMLEX AMERICA INC.
Parameter Setup
Enter Key
SELECT GROUP
POWER SAVING
OTHER FUNCTION
Enter Key
SELECT GROUP
POWER SAVING
OTHER FUNCTION
Enter Key
SELECT GROUP
POWER SAVING
OTHER FUNCTION
Enter Key
SELECT GROUP
POWER SAVING
OTHER FUNCTION
Enter Key
SELECT GROUP
POWER SAVING
OTHER FUNCTION
will change over from "Inverting Mode" to
TM
Up Key x 4
RELAY FUNCTION
1 = Enable
2 = Generator 0
Up Key x 5
COMM. ID
1 = Enable
Up Key x 6
BUZZER
1 = Enable
1 = On
Up Key x 7
DISCHARGE BEEP
1 = Enable
0 = Off
Up Key x 8
DEFAULT RESET
1 = Enable
0 = No
Enter Key
KEY IN PASSWORD
0000
Password 8052
See Section 4.3.1
Enter Key
KEY IN PASSWORD
0000
1
Password 8052
See Section 4.3.1
Enter Key
KEY IN PASSWORD
0000
Password 8052
See Section 4.3.1
Enter Key
KEY IN PASSWORD
0000
Password 8052
See Section 4.3.1
Enter Key
KEY IN PASSWORD
0000
Password 8052
See Section 4.3.1
APPENDIX A
will change over to
TM
RELAY FUNCTION
2 = Generator 0
COMM. ID
001
BUZZER
1 = On
DISCHARGE BEEP
0 = Off
DEFAULT RESET
0 = No