SECtION 4 |
ReSet VoLtAGe:
This is the reset voltage at which the unit will revert to "Charging Mode" after it has
switched over to "Inverting Mode" due to input voltage falling to "CUT-OFF VOLT 1/CUT-OFF
VOLT 2/CUT-OFF VOLT3".
Up Key x 2
SELECT GROUP
CHARGE CURVE
CUt oFF VoLt 1:
If during "Charging Mode", the AC input voltage falls below "CUT-OFF VOLT 1" for period >
"DETECT TIME 1", the EVO
Mode".
Up Key x 2
SELECT GROUP
CHARGE CURVE
DeteCt tiMe 1:
This is the time limit in cycles up to which low AC input voltage "CUT-OFF VOLT 1" is allowed.
Up Key x 2
SELECT GROUP
CHARGE CURVE
CUt oFF VoLt 2:
If during "Charging Mode", the AC input voltage falls below "CUT-OFF VOLT 2" for period >
"DETECT TIME 2", the EVO
Up Key x 2
SELECT GROUP
CHARGE CURVE
DeteCt tiMe 2:
This is the time limit in cycles up to which low AC input voltage "CUT-OFF 2" is allowed.
Up Key x 2
SELECT GROUP
CHARGE CURVE
CUt oFF VoLt 3:
If during "Charging Mode", the AC input voltage falls below "CUT-OFF VOLT 3" for period >
"DETECT TIME 3", the EVO
Up Key x 2
SELECT GROUP
CHARGE CURVE
DeteCt tiMe 3:
This is the time limit in cycles up to which the low AC input voltage "CUT-OFF 3" is allowed.
Up Key x 2
SELECT GROUP
CHARGE CURVE
Parameter Setup
Enter Key
SELECT GROUP
RESET VOLTAGE
INPUT LOW LIMIT
Inverter/Charger will transfer to Inverting Mode from "Charging
TM
Enter Key
SELECT GROUP
RESET VOLTAGE
INPUT LOW LIMIT
Enter Key
SELECT GROUP
RESET VOLTAGE
INPUT LOW LIMIT
Inverter/Charger will transfer to "Inverting Mode".
TM
Enter Key
SELECT GROUP
RESET VOLTAGE
INPUT LOW LIMIT
Enter Key
SELECT GROUP
RESET VOLTAGE
INPUT LOW LIMIT
Inverter/Charger will transfer to "Inverting Mode".
TM
Enter Key
SELECT GROUP
RESET VOLTAGE
INPUT LOW LIMIT
Enter Key
SELECT GROUP
RESET VOLTAGE
INPUT LOW LIMIT
Enter Key
KEY IN PASSWORD
190.0 V
0000
Password 8052
See Section 4.3.1
Up Key x 1
CUT OFF VOLT 1
190.0 V
180.0 V
Up Key x 2
DETECT TIME 1
190.0 V
300 cycles
Up Key x 3
CUT OFF VOLT 2
190.0 V
170.0 V
Up Key x 4
DETECT TIME 2
190.0 V
60 cycles
Up Key x 5
CUT OFF VOLT 3
190.0 V
160.0 V
Up Key x 6
DETECT TIME 3
190.0 V
1 cycle
APPENDIX A
RESET VOLTAGE
190.0 V
Enter Key
KEY IN PASSWORD
0000
Password 8052
See Section 4.3.1
Enter Key
KEY IN PASSWORD
0000
Password 8052
See Section 4.3.1
Enter Key
KEY IN PASSWORD
0000
Password 8052
See Section 4.3.1
Enter Key
KEY IN PASSWORD
0000
Password 8052
See Section 4.3.1
Enter Key
KEY IN PASSWORD
0000
Password 8052
See Section 4.3.1
Enter Key
KEY IN PASSWORD
0000
Password 8052
See Section 4.3.1
SAMLEX AMERICA INC. | 29
CUT OFF VOLT 1
180.0 V
DETECT TIME 1
0300 cycles
CUT OFF VOLT 2
170.0 V
DETECT TIME 2
0060 cycles
CUT OFF VOLT 3
160.0 V
DETECT TIME 3
0001 cycle