Wire the AC/DC transformer to the power supply
1. The transformer block comes pre-wired with 10 feet of cable. If an extension is needed, use 18
AWG wire (minimum grade) to connect to the 16VAC/19VDC POWER INPUT terminal block on
the power supply board, using terminals DC +/AC1 and DC -/AC2.
2. To maintain UL compliance, the unit must be powered by a UL 294 Listed power supply capable
of supplying 16VAC/19VDC, 2.1A to the power supply board.
Model
Brivo ACS6000-A/ACS6008-A
Brivo ACS6000-E/ACS6008-E
© 2019 Brivo Systems LLC. All rights reserved.
WARNING: Transform Connection
DO NOT CONNECT THE TRANSFORMER TO A SWITCHED OUTLET OR OTHERWISE
CONTROLLED AC OUTLET.
DO NOT CONNECT THE TRANSFORMER TO THE 120 VAC OUTLET UNTIL ALL
WIRING IS COMPLETED.
Figure 9 - Connect AC Transformer to Power Supply
Circuit
Input
Voltage (VDC/AC)
120/240VAC (Primary)
(This voltage is supplied
to the wall transformer
and not directly to any
PCBs inside of the
chassis)
19VDC (Secondary)
16VAC (Secondary)
P-MAN-PUB-ACS6000 Installation Manual
21
Brivo ACS6000 Installation Manual
Current (mA/A)
0.49A/1.0A
1.89A (DC)
2.25 A (RMS)