Download Print this page

Advertisement

BRIVO ACS6000
INSTALLATION MANUAL
© 2019 Brivo Systems LLC. All rights reserved.
P-MAN-PUB-ACS6000 Installation Manual
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the ACS6008 and is the answer not in the manual?

Questions and answers

Summary of Contents for Brivo ACS6008

  • Page 1 BRIVO ACS6000 INSTALLATION MANUAL © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 2 ACS6008 Parts and Service The ACS6000 control panel contains no user serviceable parts. The lithium battery is not serviceable and is to be replaced by qualified service technicians only. © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 3 Brivo Systems LLC. The information contained within this document or within the product itself is considered the exclusive property of Brivo Systems LLC. All information in this document or within the hardware and software product themselves is protected by the copyright and/or other intellectual property laws of the United States.
  • Page 4: Table Of Contents

    Table of Contents INTRODUCTION ..........................5 PRE-INSTALLATION PROCEDURES ....................7 GENERAL ASSEMBLY PROCEDURES ....................13 INSTALLATION PROCEDURES ......................22 POWERING AND TESTING PROCEDURES ..................38 CONFIGURATION PROCEDURES ....................40 © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 5: Introduction

    ACS6000 Control Panel at client sites. This version of the manual is also intended for IT personnel, who should use it in conjunction with the Brivo Panel Networking Admin Interface Guide. It may be used by dealers and their sales professionals to help them conduct pre-sales, and to provide client support during the installation process.
  • Page 6 Installation Worksheet: Input Output Board • Brivo Onair Quick Start Guide • Brivo Cellular Network Router Configuration Guide • Brivo Onsite Server Quick Start Guide • Technical Support: 1-866-BRIVO-4-U • www.brivo.com © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 7: Pre-Installation Procedures

    Brivo ACS6000 Installation Manual PRE-INSTALLATION PROCEDURES Before you begin installing the Brivo control panel, perform the following tasks to ensure a safe, speedy, and successful installation. Understand the function of the Brivo ACS6000 control panel. The ACS6000-E and ACS6000-A are four (4) reader control panels with multiple access points (up to four readers per chassis).
  • Page 8 Brivo ACS6000 Installation Manual 3. For Brivo Onair accounts, make sure the account has been created and the control panel is registered through Brivo Onair. If the control panel has not been registered by the dealer, the installer may either contact Brivo Technical Support for assistance or simply register the panel directly.
  • Page 9 Expansion Chassis Kit (B-ACS6000-EXP) or Large Expansion Chassis Kit (B- ACS6008-EXP). Each standard expansion chassis can hold up to two boards, including any combination of door and/or Input Output boards. Each large expansion chassis can hold up to four boards, including any combination of door and/or Input Output boards.
  • Page 10 An INPUT OUTPUT BOARD cannot be used to control a door; however, it can be used in any circumstance that uses contact closure to track change of status. d. Each large expansion chassis (ACS6008) may contain up to four boards, in any combination of DOOR BOARDs and/or INPUT OUTPUT BOARDs.
  • Page 11 ACS6000 does not specify a maximum distance between the chassis and a keypad or reader, but the keypad/reader manufacturer does. Follow manufacturer guidelines for each keypad and reader. Place each chassis within 500 feet of its associated electronic strike or latch. © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 12 UPS (Uninterruptible Power Supply) between the AC Mains and the transformer. © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 13: General Assembly Procedures

    Make sure the chassis door can swing open freely to allow for access after the installation is complete. In tight spaces, the removable hinge design of the ACS6000/ACS6008 enclosures allow an installer to completely remove the chassis door and replace it just as easily upon completion of the installation.
  • Page 14 7. OPTIONAL: Install the physical tamper switch in the chassis. Install the tamper switch in the chassis by removing the hex collar, seating the switch inside the provided mounting bracket, and reattaching and tightening the hex collar. © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 15 Brivo ACS6000 Installation Manual Switch SW 7 setting description Figure 1 - ACS6000 SW 7 Switch Bank Location Figure 2 - ACS6000 SW 7 Switch Settings © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 16 Diagnostic Enabled: MCU Full Debug Disabled: MCU Standard Debug SW 7-8 Wi-Fi Enabled: Wi-Fi can be used if configured. Disabled: Wi-Fi cannot be used at all, even if configured. © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 17 Ground, Power Detection, and Earth Ground to each board from the power supply. WARNING: Power Supply DO NOT USE ANY POWER SUPPLY OTHER THAN THOSE SUPPLIED WITH YOUR BRIVO PRODUCT. © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 18 DO NOT POWER ELECTRONIC STRIKES AND LATCHES WITH THE BATTERY (OR OTHER POWER SOURCE) USED TO POWER THE CONTROL PANEL; DOING SO WILL CAUSE DAMAGE TO THE BRIVO CONTROL PANEL. USE ONLY A UL LISTED BURGLAR ALARM OR ACCESS CONTROL SYSTEM TO POWER ELECTRONIC STRIKES AND LATCHES.
  • Page 19 Connect the battery leads to the power supply WARNING: Backup Battery DO NOT CONNECT THE BACK-UP BATTERY AT THIS TIME. Premature connection of the battery terminals may cause damage to the control panel. © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 20 Make sure the battery wires are segregated at least ¼ inch away from all other input/output wiring. NOTE: Power Standby Level 1 for UL listed systems. Figure 8 - Connect Battery Leads to Power Supply © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 21 0.49A/1.0A and not directly to any Brivo ACS6000-A/ACS6008-A Input PCBs inside of the Brivo ACS6000-E/ACS6008-E chassis) 19VDC (Secondary) 1.89A (DC) 16VAC (Secondary) 2.25 A (RMS) © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 22: Installation Procedures

    If connecting two door/IO boards, use the first and second larger board connectors. In an ACS6008 enclosure, you have the option to connect a mainboard to three door/IO boards or to connect four door/IO boards together using the provided pre-assembled CAN Bus cable.
  • Page 23 • Wire E3 to E2 in Expansion Chassis 1. • Wire E2 in Expansion Chassis 1 to E1 in the Control Chassis. • Wire E1 to the MAIN BOARD. © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 24 9. Connect the CAN NODE ADDRESS jumpers. The silkscreen next to the CAN NODE ADDRESS pins shows how to position the jumpers for first four addresses. 10. Positions for additional address values are shown in the diagram below. © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 25 1 is the MAIN BOARD. Record all addresses on the Installation Worksheet. These jumper settings will map to board numbers when the control panel is configured via the application. © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 26 NOTE: ACS6000 Output Ratings for the ACS6000 Main Board • Two (2) reader ports, 12V, 350mA each • Two (2) selectable wet contacts, 12VDC, 350mA each • Four (4) dry contacts are 28VDC, 6A each © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 27 NOTE: The fully programmable AUX RELAYs provide both NO (Normally Open) and NC (Normally Closed) contacts. WARNING: Relay Amp Limit THERE IS A 3A, 24VDC LIMIT ON THROUGH CURRENT FOR ALL RELAYS. © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 28 NOTE: Any device at the end of the RS-485 bus needs to be terminated using a 120�� resistor. This resistor may be built into the device or may need to be added externally. © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 29 Door 1 FDX/HDX switch on Door 1 and Door 2 FDX/HDX switch on Door 2 to the Full-Duplex position. If placing into Full-Duplex mode, be careful as most readers will typically operate in Half-Duplex mode. © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 30 To enable RS-485 bus termination for Door 1, put the RS-485 termination switch in the Enabled position. To enable RS-485 termination for Door 2, put the RS-485 termination switch in the Enabled position. © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 31 To enable dry mode for Door 2, put the Door 2 Wet/Dry Select Switch in the Dry position. Figure 19 - ACS6000 Wet/Dry Door Contact Switches for Doors 1 and 2 © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 32 Connect the wire to the GND terminal. This is the standard Ground circuit for OSDP readers using RS-485. • Connect the wire to the 12VDC terminal. This provides +12VDC to power OSDP readers using RS-485. © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 33 Use the wire recommended by the manufacturer of the electric strike or latch. If no wire is recommended, use a minimum of 18 AWG wire with sufficient strands for the specific electronic strike or latch. © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 34 1 from the switch, while the other end is connected to the wire leading to the ACS6000 control board. e) The other wire from the ACS6000 is connected to wire 2 from the switch, as shown in Figure 21. © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 35 DO NOT POWER ELECTRONIC STRIKES AND LATCHES WITH THE BATTERY (OR OTHER POWER SOURCE) USED TO POWER THE CONTROL PANEL; DOING SO WILL CAUSE DAMAGE TO THE BRIVO CONTROL PANEL. USE ONLY A UL LISTED BURGLAR ALARM OR ACCESS CONTROL SYSTEM TO POWER ELECTRONIC STRIKES AND LATCHES.
  • Page 36 5. Attach the silver end of the Wi-Fi integrated circuit antenna connector located in the upper right hand corner of the Wi-Fi antenna chip on the ACS6000 MAIN BOARD. Figure 24 – Wi-Fi Integrated Circuit Antenna Connector © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 37 2. Use 18 AWG or larger wire to connect the chassis to a suitable earth ground. 3. The ground contact point is in the lower panel area, near the hinge for the door and in front of the power supply. © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 38: Powering And Testing Procedures

    1. Plug the transformer into a 120VAC outlet. NOTE: Firmware Upgrade at First Time Connect When first registered and connected to the Brivo Onair cloud service, your ACS300 will automatically download and install the latest firmware. This process may take several minutes, so do not disconnect or cut power to your ACS300 during this process.
  • Page 39 NOTE: A steady light is an indication of a problem, just as much as no light is. 3. If ALL power indicators are correct, attach the back-up battery and check that ALL indicators remain the same. © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 40: Configuration Procedures

    The LAN port is a 10/100/1000 Ethernet interface with an RJ45 jack for connecting the MAIN BOARD to a Local Area Network in order for it to gain connectivity to the Internet and the appropriate server depending upon the version of MAIN BOARD. © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 41 OSDP readers assigned to the same control panel. However, make certain that the default OSDP reader address matches the OSDP address used when assigning the reader in Brivo Onair. © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...
  • Page 42 CAN Bus connection cable Added RS-485 bus 06/19/2019 configuration/termination information 1.10 05/13/2020 Added first time connect firmware upgrade note 1.11 08/06/2020 Added OSDP addressing clarification P-MAN-PUB-ACS6000 Installation Manual_v1.11 © 2019 Brivo Systems LLC. All rights reserved. P-MAN-PUB-ACS6000 Installation Manual...

This manual is also suitable for:

Acs6000Acs6000-02