Figure 5-6. Distributed bypass Pull-Chain wiring with MOBs
NOTE
NC and NO designations on MOB AUX contacts are defined with breaker in OFF (open) position.
If MOB contacts have pigtail leads, use the same wire gauge to connect to the UPS and use the
correct crimp connections for the wire gauge.
External CAN connections between UPS cabinets require shielded twisted pair wire.
Use twisted pair wiring between the UPS and MOB AUX contacts.
Always confirm contact operation prior to wiring.
59
9395P 250 kVA / 275 kVA / 300 kVA
User's and Installation Guide