Figure 5‐6. Distributed Bypass Pull-Chain Wiring With Mobs - Eaton PowerXpert 9395P-600/600 Installation And Operation Manual

Powerxpert 9395 high performance (9395p-600) ups
Hide thumbs Also See for PowerXpert 9395P-600/600:
Table of Contents

Advertisement

Shielded Twisted Pair
UPS 1
CAN Bridge Card J3
MOB 1
AUX 1
AUX 2
TB1
7
8
9
10
TB2
1
2
3
4
5
6
7
8
9
10
UPS 1
NOTE NC and NO designations on MOB AUX contacts are defined with breaker in OFF (open) position.
NOTE If MOB contacts have pigtail leads, use the same wire gauge to connect to UPS and use the correct crimp connections for the wire gauge.
NOTE External CAN connections between UPS cabinets require shielded twisted pair wire.
NOTE Use twisted pair wiring between the UPS and MOB AUX contacts.
NOTE Always confirm contact operation prior to wiring.
Eaton Power Xpert 9395P-600 (380V-600V) UPS Installation and Operation Manual
Shielded Twisted Pair
Twisted Pair
Twisted Pair
UPS 2
CAN Bridge Card J3
MOB 2
NC
NC
COM
AUX 1
NO
NO
NC
NC
COM
AUX 2
NO
NO
TB1
7
8
9
10
TB2
1
2
3
4
5
6
7
8
9
10
UPS 2
Figure 5‐6. Distributed Bypass Pull-Chain Wiring with MOBs
INSTALLING OPTIONS AND ACCESSORIES
Shielded Twisted Pair
Twisted Pair
UPS 3
CAN Bridge Card J3
(If Installed)
Customer-Supplied Tie Cabinet
MOB 3
NC
COM
AUX 1
NO
NC
COM
AUX 2
NO
TB1
7
8
9
10
TB2
1
2
3
4
5
6
7
8
9
10
UPS 3
(If Installed)
S
www.eaton.com/powerquality
P-164000710 Rev 1
Twisted Pair
UPS 4
CAN Bridge Card J3
(If Installed)
MOB 4
NC
COM
COM
AUX 1
NO
NC
COM
COM
AUX 2
NO
TB1
7
8
9
10
TB2
1
2
3
4
5
6
7
8
9
10
UPS 4
(If Installed)
5-7