Figure 5-6. Distributed Bypass Pull-Chain Wiring With Mobs - Eaton Power Xpert 9395P User And Installation Manual

500 kva / 600 kva
Hide thumbs Also See for Power Xpert 9395P:
Table of Contents

Advertisement

Figure 5-6. Distributed bypass Pull-Chain wiring with MOBs

NOTE
NC and NO designations on MOB AUX contacts are defined with breaker in OFF (open) position.
If MOB contacts have pigtail leads, use the same wire gauge to connect to the UPS and use the
correct crimp connections for the wire gauge.
External CAN connections between UPS cabinets require shielded twisted pair wire.
Use twisted pair wiring between the UPS and MOB AUX contacts.
P-164000476
Revision 002
9395P 500kVA / 600 kVA
User's and Installation Guide
59