Lenovo ThinkSystem DA240 Reference page 41

Enclosure and compute node
Table of Contents

Advertisement

1. Please check the enclosure event refer to following section
– For DW612 enclosure
– If the Shared IO mode is enabled, the auxiliary node will acquire power permisson once the
primary node is power on.
– For DA240 enclosure
– Ensure all fan modules are well installed and have no fault event.
2. If the event persists, reseat the indicated compute node if the node is under power fault condition.
(Service technician only)
3. If the event persists, reset the BMC on indicated compute node.
4. If the event persists, ensure the indicated compute node is completely power off and then reseat it.
(Service technician only)
5. If the event persists, replace the indicated compute node. (Service technician only)
6. If the event persists, please consult with technical service.
• 21070142: Node 3 Pwr Perm: Slot Or Connector, transition to Non-Critical from OK was asserted.
The indicated compute node hasn't acquired power permission to into ready state.
Severity: Warning
Alert Category: Node - Node event
SNMP Trap ID: 554107202
User Action:
1. Please check the enclosure event refer to following section
– For DW612 enclosure
– If the Shared IO mode is enabled, the auxiliary node will acquire power permisson once the
primary node is power on.
– For DA240 enclosure
– Ensure all fan modules are well installed and have no fault event.
2. If the event persists, reseat the indicated compute node if the node is under power fault condition.
(Service technician only)
3. If the event persists, reset the BMC on indicated compute node.
4. If the event persists, ensure the indicated compute node is completely power off and then reseat it.
(Service technician only)
5. If the event persists, replace the indicated compute node. (Service technician only)
6. If the event persists, please consult with technical service.
• 21070143: Node 4 Pwr Perm: Slot Or Connector, transition to Non-Critical from OK was asserted.
The indicated compute node hasn't acquired power permission to into ready state.
Severity: Warning
Alert Category: Node - Node event
SNMP Trap ID: 554107203
User Action:
1. Please check the enclosure event refer to following section
– For DW612 enclosure
– If the Shared IO mode is enabled, the auxiliary node will acquire power permisson once the
primary node is power on.
– For DA240 enclosure
– Ensure all fan modules are well installed and have no fault event.
2. If the event persists, reseat the indicated compute node if the node is under power fault condition.
(Service technician only)
.
37