Severity: Warning
Alert Category: System - SMM2 system event
SNMP Trap ID: 403112429
User Action:
Ensure the input and output indicator is lit on and fault indicator is lit off on all power supplies.
• 180701F0: PSoC EPOW Out: Chassis, transition to Non-Critical from OK was asserted.
All compute nodes are notified of power supply input lost condition. The compute nodes might shut down
immediately.
Severity: Warning
Alert Category: System - SMM2 system event
SNMP Trap ID: 403112432
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 180701F1: PSoC Throttle O: Chassis, transition to Non-Critical from OK was asserted.
All compute nodes are notified of power supply overcurrent condition. The compute nodes could enter
power throttling state and affects the performance.
Severity: Warning
Alert Category: System - SMM2 system event
SNMP Trap ID: 403112433
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 180701FB: SMM2 PrimBt Fail: Chassis, transition to Non-Critical from OK was asserted.
The SMM2 unable to boot from the primary flash bank, and instead of booting from secondary flash bank.
Severity: Warning
Alert Category: System - SMM2 system event
SNMP Trap ID: 403112443
User Action:
1. Ensure the populated compute nodes are completely power off, and then reseat SMM2. (Service
technician only)
2. If the event persists, update the SMM2 firmware to latest release. (Service technician only)
3. If the event persists, replace the SMM2. (Service technician only)
4. If the event persists, please consult with technical service.
• 180702EE: PSU Type Mismtch: Chassis, transition to Critical from less severe was asserted.
The populated power supplies are composed of different types.
30