– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 086F01B7: PSU 2 Vout OV: Power Supply, Power Supply Failure detected was asserted.
The indicated power supply reports its output voltage reaches the overvoltage lockout limit.
Severity: Error
Alert Category: PSU - Power Supply event
SNMP Trap ID: 141492663
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 086F01BF: PSU 1 Vout UV: Power Supply, Power Supply Failure detected was asserted.
The indicated power supply reports its output voltage reaches the undervoltage lockout limit.
Severity: Error
Alert Category: PSU - Power Supply event
SNMP Trap ID: 141492671
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 086F01C0: PSU 2 Vout UV: Power Supply, Power Supply Failure detected was asserted.
The indicated power supply reports its output voltage reaches the undervoltage lockout limit.
Severity: Error
Alert Category: PSU - Power Supply event
SNMP Trap ID: 141492672
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 086F01C8: PSU 1 OverTemper: Power Supply, Power Supply Failure detected was asserted.
The indicated power supply reports the internal sensing device reaches warning temperature and persists
over 30 seconds.
Severity: Error