Lenovo ThinkSystem DA240 Reference page 26

Enclosure and compute node
Table of Contents

Advertisement

User Action:
1. Ensure the indicated fan module properly installed.
2. If the event persists, reseat the indicated fan module.
3. If the event persists, reseat the indicated fan cable. (Service technician only)
4. If the event persists, replace the indicated fan module. (Service technician only)
5. If the event persists, please consult with technical service.
• 04080078: Fan 3: Fan sensor, Device Removed / Device Absent was asserted.
The indicated fan module is not correctly install on the fan slot.
Severity: Error
Alert Category: Thermal - System Thermal event
SNMP Trap ID: 67633272
User Action:
1. Ensure the indicated fan module properly installed.
2. If the event persists, reseat the indicated fan module.
3. If the event persists, reseat the indicated fan cable. (Service technician only)
4. If the event persists, replace the indicated fan module. (Service technician only)
5. If the event persists, please consult with technical service.
• 0807019B: PSU 1 Throttle: Power Supply, transition to Non-Critical from OK was asserted.
The indicated power supply reports a risky condition to being shut down owing to an overcurrent or
overtemperature condition.
Severity: Warning
Alert Category: PSU - Power Supply event
SNMP Trap ID: 134676891
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 0807019C: PSU 2 Throttle: Power Supply, transition to Non-Critical from OK was asserted.
The indicated power supply reports a risky condition to being shut down owing to an overcurrent or
overtemperature condition.
Severity: Warning
Alert Category: PSU - Power Supply event
SNMP Trap ID: 134676892
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 08070792: PSU 1 EPOW: Power Supply, Monitor was asserted.
22
ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference