Nfpa Standard-Specific Requirements - Honeywell Fire-Lite Alarms MS-9050UD Manual

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms MS-9050UD:
Table of Contents

Advertisement

APPENDIX C
The MS-9050UD has been designed for use in commercial, industrial and institutional applications
and meets the requirements for service under the National Fire Protection Association (NFPA)
Standards outlined in this Appendix. The minimum system components required for compliance
with the appropriate NFPA standard are listed below:
MS-9050UD Control Panel
Contains the main control board, cabinet (backbox and door), main power supply transformer and
power supply.
Batteries
Refer to "Power Supply Calculations" on page 179, for Standby Power Requirements.
Initiating Devices
Connected to one of the control panel's Initiating Device Circuits.
Notification Appliances
Connected to the control panel's Notification Appliance Circuits via a control module.
The following additional equipment is needed for compliance with the NFPA 72 standards listed
below:
NFPA 72 NATIONAL FIRE ALARM STANDARDS FOR:
NFPA 72 Central Station Service (Protected Premises Unit) or Remote Station Service
NFPA 72 Auxiliary Fire Alarm System
4XTMF Transmitter Module for connection to a compatible listed Local Energy Municipal Box.
This unit must be installed as illustrated in the section titled "4XTMF Transmitter Module
Installation" on page 48 and as outlined in Figure C.1, "Municipal Box Connected to 4XTMF
Transmitter Module," on page 190.
NFPA 72 Proprietary Fire Alarm System
MS-9050UD Alarm, Trouble and Supervisory contacts connected to Transmitter(s). See Figure
C.3, "Proprietary Protective Signaling System," on page 192, for installation instructions for this
unit.
MS-9050UD PN 52413:C 01/23/08

NFPA Standard-Specific Requirements

Onboard Digital Alarm Communicator Transmitter for connection to a compatible
listed Central Station DACR or Protected Premises Receiving Unit. This unit must
be installed as outlined in "Digital Alarm Communicator/Transmitter" on page 16.
OR
4XTMF Transmitter Module for connection to the Fire-Lite RS82 Remote Station
Receiver. See Figure C.2, "Remote Station Connection Using 4XTMF Module," on
page 191, for installation instructions for this unit.
NFPA Standard-Specific Requirements
189