Trouble Reminder; Canadian Option; Charger Disable; 5: Option Modules - Honeywell Fire-Lite Alarms MS-5UD Series Manual

Fire alarm control panels
Table of Contents

Advertisement

Master Programming Level
SYSTEM SETUP
1=TROUBLE REMIND
NO
2=CANADIAN OPTION OFF
3=CHARGR DISABLE
NO
System Setup Screen #2
3.5.5 Option Modules
PROGRAMMING
1=SYSTEM SETUP
2=OPTION MODULES
3=HISTORY
Programming Screen #2
MS-5UD & MS-10UD Series Manual — P/N 52626:C2 1/24/2012

Trouble Reminder

The Trouble Reminder features causes the control panel piezo to sound a reminder 'beep' for
alarms and troubles, after the panel has been silenced. Refer to "System Setup" on page 75, for a
detailed description of this feature. Pressing 1 while viewing System Setup Screen #2 will cause
the display to toggle to Trouble Rem Yes, which enables this feature. Each press of the 1 key will
cause the display to toggle between Trouble Rem Yes and Trouble Rem No.
Note that if the Trouble Reminder feature is not enabled, a trouble existing on the panel for more
than 24 hours will cause the FACP to resound the trouble sounder.

Canadian Option

Pressing 2 while viewing System Setup Screen #2 will configure the FACP to comply with Cana-
dian requirements. The display will change to Canadian Opt. On. Each press of the 2 key will
cause the display to toggle between Canadian Opt. On and Canadian Opt. Off. The factory default
setting is Canadian Opt. Off.
For Canadian applications, remote annunciation must be done using the secondary ANN-BUS.
The Canadian Options configures the FACP with the following as required by Canada:
The following zone type codes are not available:
non-latching supervisory
non-latching drill
process monitor (latching or non-latching)
hazard
tornado
medical alert
combo autoresettable
The auto-silence feature can be enabled or disabled. If this feature is enabled, the alarm signals
will be turned off after 20 minutes of activation
The installer must write in the Date of Final Assembly on the Master Marking and Warranty
label, located on the FACP backbox door

Charger Disable

Pressing 3 while viewing System Setup Screen #2 will allow the programmer to enable or disable
the onboard battery charger. If an external battery charger is being used, the onboard battery char-
ger must be disabled. Each press of the 3 key will toggle between Chrgr Disable No and Chrgr
Disable Yes.
Options available for the FACP include annunciators, printer connection for acquiring hardcopy
printouts of panel data and onboard DACT.
Pressing 2 while viewing Programming Screen #2 will display the following screen:
1=ANN-BUS
2=ON BOARD DACT
OPTION MODULES
Programming
81