Ademco Contact ID Format Event Code Descriptions

APPENDIX G
This appendix describes the various Event Codes and their messages which are available for the
Ademco Contact ID Format.
G.1 Transmission Format Between DACT and Receiver
The transmission string for the Ademco Contact ID Format is as follows:
SSSS 18 QXYZ GG CCC where
SSSS
18
Q
XYZ
GG
CCC
Notes:
1. 18, which is used in the reporting structure to identify the transmission as Contact ID, is not
printed out in the alarm and trouble report.
2. GG Group Number is fixed at '00' and cannot be changed.
3. CCC for Zone or Point Number:
G.2 Ademco Contact ID Typical Printout
A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble
reports in the Ademco Contact ID Reporting Structure follows:
Time
Date
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
Notes:
1. 11 is an example of a Receiver/Line Card, showing which receiver and line card the message
was transmitted to.
2. Q, which is the Event Qualifier for the reporting structure, is printed out in the report as an E
for New Event or R for New Restore.
200
Ademco Contact ID Format
Event Code Descriptions
= Four digit Subscriber ID Account Code
= Identifies transmission as Contact ID to the receiver at the Central Station
= Event Qualifier where 1 = New Event and 3 = New Restore
= Event code
= Group number
= Zone/Point number
Zone Number is transmitted as '00' for zone 0 up to '19' for zone 19
Point Number is transmitted as '01' for point/address 1 up to '50' for point/address 50
Rcvr/Line ID
SSSS
11
7777
11
7777
11
7777
11
7777
11
7777
11
7777
11
7777
11
7777
11
7777
11
7777
QXYZ
GG
CCCC
E110
00
C001 - general fire alarm on zone one
E111
00
C002 - smoke detector alarm on zone two
E380
00
C003 - fault on zone three
E570
00
C009 - Zone nine disabled
R110
00
C001 - Zone one alarm restored
R111
00
C002 - smoke detector zone two restored
R380
00
C003 - zone three fault restored
R570
00
C009 - zone nine reenabled
E158
00
C006 - high temperature, zone six
E151
00
C007 - gas detected, zone seven
MS-9050UD PN 52413:C 01/23/08