1.8.4 Battery Box

BB-26
The BB-26 battery box may be used to house up to two 26 AH batteries and the CHG-75 Battery
Charger. The battery box, which is red and is provided with knockouts, was designed specifically
to compliment mounting below the FACP.
BB-55F
The BB-55F battery box may be used to house two 26 AH batteries, two 60 AH batteries or one
100 AH battery. When the CHG-120F is mounted in the BB-55F, two 26 AH or one 60 AH battery
may also be housed in the battery box.

1.8.5 Battery Charger

1.8.5.1 CHG-75 Battery Charger
The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the FACP. The FACP
battery charger must be disabled, by removing jumper JP30, when using the CHG-75. The
charger and up to 26 AH batteries can be housed in the BB-26 battery box. Larger batteries and
the charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away
from the control panel. Refer to the CHG-75 Manual for additional information.

1.8.5.2 CHG-120F Battery Charger

The CHG-120F is capable of charging up to 120 AH lead-acid batteries with the FACP. The
FACP battery charger must be disabled, by removing jumper JP30, when using the CHG-120F.
The batteries and charger can be housed in the BB-55F battery box which can be mounted up to
20 feet away from the control panel. Note that when using the BB-55F for housing the charger
and batteries greater than 26AH, multiple BB-55Fs are required. Refer to the CHG-120F
Manual for additional information.