Facp With Keltron - Honeywell Fire-Lite Alarms MS-9050UD Manual

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms MS-9050UD:
Table of Contents

Advertisement

APPENDIX D
The following figure illustrates the connections between the FACP and Keltron Receiver/
Transmitter.
CAUTION! For reasons of wiring diagram clarity, terminal designations of Keltron modules are
not shown in actual order. Follow Keltron manual and module markings for exact terminal
locations to prevent severe module damage!
IMPORTANT! All connections between the FACP and Keltron modules must be made within 20
feet and enclosed within conduit or equivalently protected against mechanical injury.
Keltron 95M3158 TTM-RPS
1. Terminals 7 and 8: Remote station alarm/trouble inputs.
2. Terminals 9 and 10: Sprinkler supervisory input.
MS-9050UD PN 52413:C 01/23/08

FACP with Keltron

Sprinkler Supervisory Signal
4XTMF Module
Note: Cut TBL jumper on 4XTMF module to send
alarm/trouble signal from the same pair or terminals.
Fire Alarm Control Panel
(terminal blocks are not shown in
their actual positions in order to
clarify wiring connections)
Figure D.1 FACP With Keltron Wiring
*Note: For more information,
refer to Keltron manual.
Alarm/Trouble Signal
FACP with Keltron
195

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fire-lite alarms ms-9050udc

Table of Contents