Programming
Monitor module type selection will affect the function of the point as follows:
Monitor Type
Pull-Station
User-Defined-1
Waterflow
User-Defined-2
Monitor
User-Defined-3
Future Use
Future Use
Smoke-Conventional
User-Defined-5
Heat-Conventional
User-Defined-6
Medic-Alert
User-Defined-7
Hazard-Alert
User-Defined-8
Tornado-Alert
User-Defined-9
Future Use
Future Use
Tamper
User-Defined-11
Supervisory
User-Defined-12
Supervisory-AR
User-Defined-13
HVAC OVRRIDE
Power-Monitor
User-Defined-14
Trouble-Monitor
User-Defined-15
Proc-Mon
User-Defined-16
Procmon-AR
User-Defined-17
Future Use
Future Use
Ack-Switch
Sil-Switch
Reset-Switch
Drill-Switch
PAS-Bypass
HVAC RESTART
Drill-Switch AR
Notes:
1. For entries ending in AR, AR refers to AutoResettable.
2. For HVAC RESTART AND HVAC OVRRIDE descriptions, refer to "HVAC Control" on
page 198.
3. Drill Switch Auto-Resettable turns on the NACs and any control module mapped to the Drill
Switch zone.
4. Conventional 2-wire smoke detectors may be powered using an external power supply with
an SLC Control Relay Module programmed for Resettable Power operation. A Control
Relay Module set to the Resettable Power type will follow the main circuit board 24 VDC
resettable power unless the control module is disabled.
5. Use only these Monitor Type IDs for the Zone Modules (MMF-302). The Zone Modules
will not function correctly if any other Type ID is used.
6. Combination systems employing these non-fire monitor types require the SLC loop to be
programmed by the installer for Style 4 operation and isolator modules must be employed on
each non-fire branch of the SLC as per Figure 13 in the SLC Wiring Manual (document
number 51309). Fire and non-fire devices must not be used on the same SLC branch.
72
Table 3.1 Monitor Types
4, 5
5
5
5
6
6
6
1
6
1, 6
1
Action When Activated
Fire Alarm
Fire Alarm
Fire Alarm Delayed (uses waterflow delay)
Fire Alarm Delayed (uses waterflow delay)
Fire Alarm
Fire Alarm
Future Use
Future Use
Fire Alarm
Fire Alarm
Fire Alarm
Fire Alarm
Supervisory, latching
Supervisory, latching
Supervisory, latching
Supervisory, latching
Supervisory, latching
Supervisory, latching
Future Use
Future Use
Supervisory, nonlatching (tracking)
Supervisory, nonlatching (tracking)
Supervisory, latching
Supervisory, latching
Supervisory, nonlatching (tracking)
Supervisory, nonlatching (tracking)
Switch Supervisory, nonlatching (tracking)
AC Fault
AC Fault
Trouble
Trouble
Piezo
Piezo
Piezo, nonlatching (tracking)
Piezo, nonlatching (tracking)
Future Use
Future Use
Acts like panel Acknowledge Key
Acts like panel Alarm Silence Key
Acts like panel Reset Key
Acts like panel Drill Key
PAS Disable
Switch
Acts like panel Drill Key, nonlatching (tracking)
MS-9050UD PN 52413:C 01/23/08