Programming
CENTRAL STATION
1=EVENT CODES
Primary/Secondary Screen #4
126
The Communication Format is determined by the type of receiver that the DACT is transmitting
to. Consult your Central Station for proper selection or consult our factory representatives.
For any format chosen, the control panel automatically programs all of the event codes.
Select the Communication Format by pressing the corresponding number key while viewing the
appropriate Comm Format screen. The following table describes each format:
Table 3.2 Communication Formats
Screen Selection
ADEMCO EXPRESS 4P1
ADEMCO EXPRESS 4P2
3P1S C18 A23
3P1E C18 A23
3P1S C19 A14
3P1E C19 A14
4P1S C18 A23
4P1E C18 A23
4P1S C19 A14
4P1E C19 A14
4P2S C18 A23
4P2E C18 A23
4P2S C19 A14
4P2E C19 A14
ADEMCO CONTACT ID
Event Codes
Pressing 1 while viewing Primary/Secondary Screen #4 will cause the following screen to be
displayed:
EVENT CODES
1=PULL STATION
2=MON-USER-DEF-1
3=WATERFLOW
Pressing the down arrow key allows viewing of all Events associated with the selected
Communication Format. Pressing the number corresponding to the event displayed in each
screen will display its default event code which can be customized by the programmer. For
example, pressing 1 for Pull Station will display the following screen which allows the Event
Code to be changed from the default value.
PULL STATION
The tables on the following pages list all of the Events and their default Event Codes for the
various Communication Formats.
Communication Format Description
4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
Contact ID, DTMF, 1400/2300 ACK
Event Code Screen
Event Code Screen
115