Pressing 3 for View Summary while viewing the Unit In Walktest screen will display a new screen
which will show a total of the tested detectors, tested modules, untested detectors and untested
modules for the current walktest session.
The user can perform a one-person walktest by activating devices throughout the system. As each
device is activated, the information about the activated device is store in the Walktest Log. The
information can be viewed by choosing one of the options from the Unit In Walktest screen.
After completion of the Walktest, press the Esc (Escape) key to exit Walktest Mode and return to
the Walktest Screen. The results of the Walktest can now be viewed by pressing 3 while viewing
the Walktest Screen. The following screen will be displayed:
Use the up and down arrow keys to view all of the walktest results which will be displayed as
illustrated in the preceding screen. Note that the Walktest log is stored in RAM. If all power (AC
and DC) is removed from the FACP, the Walktest log information will be lost. This information is
also overwritten when subsequent walktests are performed.

3.6.9 Option Modules

Options available for the MS-9050UD include annunciators, printer connection for acquiring
hardcopy printouts of panel data and onboard DACT.
Pressing 3 while viewing Programming Screen #3 will display the following screen:
PROGRAMMING
1=HISTORY
2=WALKTEST
3=OPTION MODULES
Programming Screen #3
MS-9050UD PN 52413:C 01/23/08
WALKTEST RESULTS
View Result Screen
OPTION MODULES
1=ANN-BUS
2=ONBOARD DACT
Options Screen
Programming
105