4.7 Process Monitor Operation

Process Monitor operation will initiate the following events:
The piezo sounder pulses ¼ second On and ¼ second Off
The LCD displays a process monitor message along with the device name, type, address,
adjective/noun, associated zones and time/date
Communicate the process monitor condition to the Central Station
Relays programmed for process monitoring will be activated
The alarm relay is not activated
NACs will not activate
Timers are not started
Store event in history buffer
Note that, like supervisories, process monitor signals latch (except when programmed for process
monitor autoresettable) and can be assigned to software zones.

4.8 Hazard/Tornado Condition Operation

Hazard/Tornado Condition operation will initiate the following events:
The piezo sounder pulses ½ second On, ½ second Off
The LCD displays a hazard message along with the device name, type, address, adjective/
noun, associated zones and time/date
Communicate the hazard condition to the Central Station
Relays programmed for hazard will be activated
The alarm relay is not activated
NACs will not activate
Timers are not started
Store event in history buffer
Supervisory LED flashes ½ second On, ½ second Off
Hazard conditions latch. They can be assigned to software zones.

4.9 Medical Alert Condition Operation

Medical Alert Condition operation will initiate the following events:
The piezo sounder ½ second On, ½ second Off
The LCD displays a medical alert message along with the device name, type, address,
adjective/noun, associated zones and time/date
Communicate the medical alert condition to the Central Station
Relays programmed for medical alert will be activated
The alarm relay is not activated
NACs will not activate
Timers are not started
Store event in history buffer
Supervisory LED flashes ½ second On, ½ second Off
Medical alert conditions latch. They can be assigned to software zones.

4.10 NAC Operation

There are two programmable NACs (Notification Appliance Circuits) resident on the MS-9050UD
main circuit board which can be wired for Style Y (Class B) or Style Z (Class A) . Both NACs may
be programmed as silenceable or nonsilenceable and may also be programmed for steady or coded
operation. Coded operation provides a choice between March Time, Temporal or California
coding.
MS-9050UD PN 52413:C 01/23/08
Operating Instructions