Honeywell Fire-Lite Alarms MS-9050UD Manual page 73

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms MS-9050UD:
Table of Contents

Advertisement

EDIT MONITOR
1=PRE-SIGNAL
Edit Monitor Screen #3
See Page
EDIT MONITOR
1=WALKTEST
2=ZONE ASSIGNMENT
00 ** ** ** **
Edit Monitor Screen #4
EDIT MONITOR
1=NOUN/ADJECTIVE
2=DESCRIPTION
*****************
Edit Monitor Screen #5
MS-9050UD PN 52413:C 01/23/08
Pre-signal
To enable the Pre-signal feature, press 1 while viewing Edit Monitor Screen #3 until the display
reads Pre-signal Yes. Each press of the 1 key will cause the display to toggle between Pre-
signal Yes and Pre-signal No. Refer to "Presignal" on page 155 for additional information.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of
manually resetting the control panel after each device activation. To enable devices, which are
connected to a monitor module, for the Walktest feature, press 1 while viewing the Edit Monitor
Screen #4 until the display reads Walktest Yes. Each press of the 1 key will cause the display to
toggle between Walktest Yes and Walktest No. Refer to "Walktest" on page 158 for additional
information.
Zone Assignment
A maximum of five zones can be programmed to each addressable monitor module. Pressing 2
while viewing Edit Monitor Screen #4 displays the following screen:
MON ZONE ASSIGN
Z00 Z** Z** Z** Z**
Note that Z** represents the Zone Number(s) corresponding to this device. The factory default
for an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on
the first 0 to the left. Enter the two digit number corresponding to the zone that is to be assigned
to this device. The cursor moves to the next Z** designation. Continue entering zone
assignments or the remaining zones can be left blank or programmed as general alarm zones
Z00. When all desired changes have been made, press the Enter key to store the zone
assignments. The display will return to the Edit Monitor Screen #4.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the
monitor module currently being programmed. Pressing 1 while viewing Edit Monitor Screen
#5 will cause the following screen to be displayed:
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Zone Assignment Screen
Noun/Adjective Screen
Programming
73