3.6.5.5.4 Auto Silence
The Auto Silence feature, when enabled, automatically silences all main circuit board
silenceable notification appliances after a programmed length of time. To enable this feature
and program the time delay before Auto Silence activation, press 1 while viewing NAC Screen
#2. The following screens will be displayed:
1=NO
2=5 MINUTES
3=10 MINUTES
Auto Silence Screen #1
1=15 MINUTES
2=20 MINUTES
3=25 MINUTES
AUTO SILENCE
1=30 MINUTES
To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1. To
enable the Auto Silence feature, press the number corresponding to the time delay which will
elapse before Auto Silence activates. This information will be stored in memory and the
display will return to NAC Screen #2.
Note: All silenceable control modules will be controlled by the Autosilence timer for NAC 1.

3.6.5.5.5 Coding (only for NACs not programmed as Sync Strobe Type)

The Coding feature allows the programmer to select the type of output that the main circuit
board notification appliances will generate when activated. Pressing 2 while viewing NAC
Screen #2 will cause the following displays to appear:
1=STEADY
2=MARCH TIME
3=CALIFORNIA
Coding Screen #1
1=TEMPORAL
2=TWO STAGE 3 MIN
3=TWO STAGE 5 MIN
AUTO SILENCE
AUTO SILENCE
Auto Silence Screen #2
Auto Silence Screen #3
CODING
CODING
Coding Screen #2
MS-9050UD PN 52413:C 01/23/08