Programming
EDIT CONTROL
1=ENABLED
2=TYPE
3=SILENCEABLE
Edit Control Screen #2
EDIT CONTROL
1=WALKTEST
2=ZONE ASSIGNMENT
00 ** ** ** **
Edit Control Screen #3
EDIT CONTROL
1=NOUN/ADJECTIVE
2=DESCRIPTION
Edit Control Screen #4
80
Silenceable
The Silenceable selection allows the programmer to select whether output devices connected to
the control module can be silenced, either by pressing the Alarm Silence key or by enabling
Autosilence. Pressing the 3 key while viewing Edit Control Screen #2 will enable the
Silenceable feature causing the display to read Silenceable Yes. Repeated presses of the 3 key
will cause the display to toggle between Silenceable Yes and Silenceable No.
Note that nonsilenceable outputs will not be activated for Fire Drill.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of
manually resetting the control panel after each device activation. To enable devices, which are
connected to a control module, for the Walktest feature, press 1 while viewing the Edit Control
Screen #3 until the display reads Walktest Yes. Each press of the 1 key will cause the display to
toggle between Walktest Yes and Walktest No. Refer to "Walktest" on page 158 for additional
information.
Zone Assignment
A maximum of five zones can be programmed to each addressable control module. Pressing 2
while viewing Edit Control Screen #3 displays the following screen:
Z00 Z** Z** Z** Z**
Note that Z** represents the Zone Number(s) corresponding to this device. The factory default
for an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on
the first 0 to the left. Enter the two digit number corresponding to the zone that is to be assigned
to this device. The cursor moves to the next Z** designation. Continue entering zone
assignments or the remaining zones can be left blank or programmed as general alarm zones
Z00. When all desired changes have been made, press the Enter key to store the zone
assignments. The display will return to the Edit Control Screen #3.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the
control module currently being programmed. Pressing 1 while viewing Edit Control Screen #4
will cause the following screen to be displayed:
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
ZONE ASSIGNMENT
Zone Assignment Screen
Noun/Adjective Screen
MS-9050UD PN 52413:C 01/23/08