Programming
Date
To change the date, press 2 while viewing the Time-Date Screen. The following screen will be displayed:
A flashing cursor is located toward the top left of the display. Below the cursor is the current date. To change the date, enter the two-digit
month followed by the two-digit day and then the two-digit year (18 for 2018, 19 for 2019 etc.). The cursor will move one position to the
right each time a digit is entered. After the last year digit is entered, the display will return to the Time-Date Screen which will show the
new date entry. If an error is made while entering a digit, press the CLR key to delete the entire entry and beginning again.
Clock Format
The clock can be configured to display 12 hour (AM & PM) or 24 hour (military) time. Pressing 3 while viewing the Time-Date screen
will cause the display to toggle between 12HR and 24HR. Select 12HR for 12 hour display or 24HR for 24 hour display.
NOTE: If the clock is changed to 24 hour (military) format, the date will change to the European standard of Day-Month-Year (for display
purposes only).
Daylight Savings Time
TIME AND DATE
1=DAYLIGHT SAVINGS
Time & Date Screen #2
Pressing 1 while viewing Daylight Savings Screen #1 will cause the display to toggle between Enabled Yes and Enabled No. The control
panel will automatically update the time for daylight savings time when Enabled Yes is selected.
Pressing 2 while viewing Daylight Savings Screen #1 will display another screen which allows the programmer to select the month that
daylight savings time will begin. In this sub-screen, pressing 1 will select March, 2 will select April, and 3 will select May.
Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-screens which allow the programmer to select the week of the
month that daylight savings time will begin. In the first sub-screen, pressing 1 will select the first week, 2 will select the second week,
and 3 will select the third week, while in the second sub-screen, pressing 1 will select the fourth week, and 2 will select the last week of
the selected month.
Pressing 1 while viewing Daylight Savings Screen #2 will display another screen which allows the programmer to select the month that
daylight savings time will end. In this sub-screen, pressing 1 will select September, 2 will select October, and 3 will select November.
Pressing 2 while viewing Daylight Savings Screen #2 will display two sub-screens which allow the programmer to select the week of the
month that daylight savings time will end. In the first sub-screen, pressing 1 will select the first week, 2 will select the second week, and
3 will select the third week, while in the second sub-screen, pressing 4 will select the fourth week, and 5 will select the last week of the
selected month.

Trouble Reminder

SYSTEM SETUP
1=TROUBLE REMIND
2=CANADIAN OPTION OFF
3=CHARGR DISABLE
System Setup Screen #2
Note that if the Trouble Reminder feature is not enabled, a trouble existing on the panel for more than 24 hours will cause the FACP to
resound the trouble sounder.

Canadian Option

Pressing 2 while viewing System Setup Screen #2 will configure the FACP to comply with Canadian requirements. The display will
change to Canadian Opt. On. Each press of the 2 key will cause the display to toggle between Canadian Opt. On and Canadian Opt. Off.
The factory default setting is Canadian Opt. Off.
For Canadian applications, remote annunciation must be done using the secondary ANN-BUS.
The Canadian Options configures the FACP with the following as required by Canada:
The following zone type codes are not available:
 non-latching supervisory
 non-latching drill
 process monitor (latching or non-latching)
 hazard
 tornado
70
Pressing 1 while viewing Time-Date Screen #2 will cause the following screens to be displayed:
DAYLIGHT SAVINGS
1=ENABLED
2=START MONTH
3=START WEEK
Daylight Savings Screen #1
The Trouble Reminder features causes the control panel piezo to sound a reminder 'beep' for alarms and
troubles, after the panel has been silenced. Refer to "System Setup" on page 67, for a detailed description of
NO
this feature. Pressing 1 while viewing System Setup Screen #2 will cause the display to toggle to Trouble
NO
Rem Yes, which enables this feature. Each press of the 1 key will cause the display to toggle between Trou-
ble Rem Yes and Trouble Rem No.
ENTER DATE
--
MONTH DAY YEAR
06-07-2018
Date Screen
YES
MAR
WK 2
SFP-5UD & SFP-10UD Series Manual— P/N 52879:C6 6/12/2018
Master Programming Level
DAYLIGHT SAVINGS
1=END MONTH
NOV
2=END WEEK
WK 1
Daylight Savings Screen #2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier sfp-10ud seriesNotifier sfp-5udNotifier sfp-5udeNotifier sfp-5udcNotifier sfp-10udNotifier sfp-10ude ... Show all

Table of Contents