Trouble Reminder; Charger Disable; Canadian Option - Honeywell MRP-2002 Instruction Manual

Agent release control system six-zone releasing fire control panel
Hide thumbs Also See for MRP-2002:
Table of Contents

Advertisement

Master Programming Level
TIME AND DATE
1=DAYLIGHT SAVINGS
Pressing 1 while viewing Time-Date Screen #2 will cause the following screens to be displayed:
Time & Date Screen #2
Pressing 1 while viewing Daylight Savings Screen #1 will cause the display to toggle between
Enabled Yes and Enabled No. The control panel will automatically update the time for daylight
savings time when Enabled Yes is selected.
Pressing 2 while viewing Daylight Savings Screen #1 will display another screen which allows the
programmer to select the month that daylight savings time will begin. In this sub-screen, pressing 1
will select March, 2 will select April and 3 will select May.
Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-screens which allow the
programmer to select the week of the month that daylight savings time will begin. In the first sub-
screen, pressing 1 will select the first week, 2 will select the second week and 3 will select the third
week, while in the second sub-screen, pressing 1 will select the fourth week and 2 will select the
last week of the selected month.
Pressing 1 while viewing Daylight Savings Screen #2 will display another screen which allows the
programmer to select the month that daylight savings time will end. In this sub-screen, pressing 1
will select September, 2 will select October and 3 will select November.
Pressing 2 while viewing Daylight Savings Screen #2 will display two sub-screens which allow the
programmer to select the week of the month that daylight savings time will end. In the first sub-
screen, pressing 1 will select the first week, 2 will select the second week and 3 will select the third
week, while in the second sub-screen, pressing 4 will select the fourth week and 5 will select the
last week of the selected month.
SYSTEM SETUP
1=TIME-DATE

Trouble Reminder

2=TROUBLE REMIND
3=CHARGR DISABLE
The Trouble Reminder features causes the control panel piezo to sound a reminder 'beep' for
System Setup Screen #2
alarms and troubles, after the panel has been silenced. Refer to "System Setup" on page 64, for a
detailed description of this feature. Pressing 2 while viewing System Setup Screen #2 will cause the
display to toggle to Trouble Remind Yes, which enables this feature. Each press of the 2 key will
cause the display to toggle between Trouble Remind Yes and Trouble Remind No.
Note that if the Trouble Reminder feature is not enabled, a trouble existing on the panel for more
than 24 hours will cause the FACP to resound the trouble sounder.

Charger Disable

Pressing 3 while viewing System Setup Screen #2 will allow the programmer to enable or disable
the onboard battery charger. If an external battery charger is being used, the onboard battery
charger must be disabled. Each press of the 3 key will toggle between Chargr Disable No and
Chargr Disable Yes.
SYSTEM SETUP

1=CANADIAN OPTION

Canadian Option
2=SEC ANN ENABLE
System Setup Screen #3
Pressing 1 while viewing System Setup Screen #3 will configure the FACP to comply with
Canadian requirements. The display will change to Canadian Opt. On. Each press of the 2 key will
cause the display to toggle between Canadian Opt. On and Canadian Opt. Off. The factory default
setting is Canadian Opt. Off.
The Canadian Options configures the FACP with the following as required by Canada:
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016
Daylight Savings Time
DAYLIGHT SAVINGS
1=ENABLED
2=START MONTH
3=START WEEK
Daylight Savings Screen #1
The following zone type codes are not available:
non-latching supervisory
non-latching drill
DAYLIGHT SAVINGS
1=END MONTH
YES
2=END WEEK
MAR
WK 2
Daylight Savings Screen #2
Programming
NOV
WK 1
69