E.1 NAC Wiring
The following table lists NAC wiring requirements for the FACP.
Max.
allowable
total loop
NAC Load
resistance
(Amps)
(ohms)
0.25
13.20
0.5
6.60
0.75
4.40
1
3.30
1.25
2.64
1.5
2.20
1.75
1.89
2
1.65
2.25
1.47
2.5
1.32
Notes: Calculations are based on Direct-Current Resistance data for uncoated copper wire, per
National Electrical Code (2005 Edition) Table 8, Conductor Properties.
MS-9050UD PN 52413:C 01/23/08
Table E.2 NAC Wiring Requirements for FACP
CLASS-B
Max. allowable wire pair length
(feet)
AWG 12
AWG 14
AWG 16
solid
solid
solid
3420
2150
1350
1710
1075
675
1140
717
450
855
537
337
684
430
270
570
358
225
489
307
193
427
269
169
380
239
150
342
215
135
CLASS-A
Max. allowable wire pair length
AWG 18
AWG 12
AWG 14
solid
solid
solid
849
1710
1075
425
855
537
283
570
358
212
427
269
170
342
215
142
285
179
121
244
154
106
214
134
94
190
119
85
171
107
Wire Requirements
(feet)
AWG 16
AWG 18
solid
solid
675
425
337
212
225
142
169
106
135
85
112
71
96
61
84
53
75
47
67
42
197