3.7.3 Program Check

Pressing 3 while viewing Maintenance Screen #1 will cause the following screen to be displayed:
PROGRAMMING
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK
Maintenance Screen #1
The Program Check feature allows the programmer to view the zones which have been
programmed to the Notification Appliance Circuits on the control panel but have not been
programmed to Initiating Devices as well as other circuits with no input or output correlations.
Pressing 1 while viewing Program Check screen will cause a screen similar to the following to be
displayed.
The example above indicates that NAC 1 has been programmed to Zones 05, 10, 12, 15 and 17 but
no input devices have been programmed to any of these zones. Use the up and down arrow keys to
view all the NAC zones without input assignments for both NAC 1 and NAC 2.
Pressing 2 while viewing the Program Check screen will display a screen similar to the following:
The Zone No Input screen allows the programmer to view the zones which have not been
programmed to at least one input device (not including general alarm Zone 00). The example in the
preceding screen indicates that Zones 05, 07, 09, 10 and 11 have been programmed to an
addressable module (control module in this example) with an address of 001 on loop 1 but have not
been programmed to any input devices. Use the up and down arrow keys to view all the zones
without input assignments.
MS-9050UD PN 52413:C 01/23/08
PROGRAM CHECK
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONE NO OUTPUT
Program Check Screen
NACS NO INPUT
NAC 1
05 10 12 15 17
ZONES NO INPUT
05 07 09 10 11 1M001
Programming