Maintenance and Troubleshooting

10.1 Routine Maintenance

Normally, the inverter and battery pack need no maintenance or calibration.
However, in order to maintain the accuracy of the SOC, it is recommended to perform a
full charge calibration for SOC (charging battery until the charging power is 0) on the
battery at regular intervals (such as two weeks).
Disconnect the inverter and battery pack from all power sources before cleaning. Clean
the housing, cover and display with a soft cloth.
To ensure that the inverter and battery pack can operate properly in the long term, you
are advised to perform routine maintenance on it as described in this chapter.
Maintenance checklist
Check Item
Product
cleanliness
Product visible
damage
Product running
status
Electrical
connections
CAUTION
Acceptance Criteria
The heatsink of the inverter are free from
obstacles or dust.
The inverter and battery pack are not damaged
or deformed.
1. The inverter and battery pack operate with
no abnormal sound.
2. All parameters of the inverter and battery
pack are correctly set. Perform this check
when the inverter and battery pack is running.
1. Cables are securely connected.
2. Cables are intact, and in particular, the
cable jackets touching the metallic surface are
not scratched.
3. Unused PV input terminals and COM ports
of the inverter, and power and COM terminals
of the battery pack are locked by watertight
caps if the product is mounted outdoor.
MAINTENANCE AND TROUBLESHOOTING
Maintenance Interval
Semiannually or once per
year
Semiannually
Semiannually
The first maintenance is
needed 6 months after the
initial commissioning. And
then make it semiannually
or once per year.