MAINTENANCE AND TROUBLESHOOTING
Error No.
Error description
INV_OTP
100035
INV_OVP
100036
INV_UVP
100037
Output_DC_
100038
over_current
INV_OCP
100039
INV_HW_OCP
100040
Output_DC_
100041
over_voltage
Output_short
100042
Output_overload
100043
Bat over-voltage alarm
110000
Bat under-voltage alarm
110001
output_overload_alarm
110002
abnormal_temperature_
110003
sensor
dc_power_alarm
110004
Solution
1. Try to lower the ambient temperature.
2. Make sure that the inverter is installed according
to the manual and there is no shelter around the
inverter.
3. After the inverter is powered off and waiting for
30 minutes, then restart it. If the fault still exists,
please call the service center.
The effective value of grid voltage exceeds the
maximum protection value of national standard
voltage.
1. Whether the off grid output terminal is short
circuited or has impact load.
2. Restart the inverter to see if the fault still exists.
If it still exists, please call the service center.
Restart the inverter to see if the fault still exists. If
it still exists, please call the service center.
1. Check whether the off grid output terminal is
overloaded, short circuited or has impact load.
2. Restart the inverter to see if the fault still exists.
If it still exists, please call the service center.
Restart the inverter to see if the fault still exists. If it
still exists, please call the service center.
1. Use a multimeter to test the impedance of the off
grid output. If it is small, check whether the wiring
is correct.
2. Restart the inverter to see if the fault still exists.
If it still exists, please call the service center.
1. Check whether the load exceeds the rated power.
2. Restart the inverter to see if the fault still exists. If
it still exists, please call the service center.
Check that the actual battery voltage is 10V higher
than the battery charging cut-off voltage
Check that the actual battery voltage is 10V higher
than the battery discharging cut-off voltage
Check whether the load exceeds 0.95 of the rated
power
Restart the inverter to see if the fault still exists. If
it still exists, please call the service center.
1. Check whether the total power of the battery
and PV is less than the load power.
2. Restart the inverter to see if the fault still exists.
If it still exists, please call the service center.
62