Error No.
Error description
MPPT1_OVP
100017
MPPT1_SW_OCP
100018
MPPT1_HW_OCP
100019
MPPT1_OTP
100020
MPPT2_OVP
100021
100022
MPPT2_SW_OCP
100023
MPPT2_HW_OCP
100024
MPPT2_OTP
BAT_OVP
100025
BAT_UVP
100026
Battery_lose
100027
BAT_OTP
100028
BAT1_charge_OCP
100029
BAT1_discharge_OCP
100030
BAT2_charge_OCP
100031
BAT2_discharge_OCP
100032
BAT1_HW_OCP
100033
BAT2_HW_OCP
100034
MAINTENANCE AND TROUBLESHOOTING
Solution
Check the PV1 voltage. If it exceeds 585VDC,
reduce the number of PV modules.
1. Try to reduce the PV power.
2. Restart the inverter to see if the fault still exists.
If it still exists, please call the service center.
1. Try to lower the ambient temperature.
2. Make sure that the inverter is installed
according to the manual and there is no shelter
around the inverter.
3. After the inverter is powered off and waiting for
30 minutes, then restart it. If the fault still exists,
please call the service center.
Check the PV2 voltage. If it exceeds 585V,
reduce the number of PV modules
1. Try to reduce the PV power.
2. Restart the inverter to see if the fault still exists.
If it still exists, please call the service center.
1. Try to lower the ambient temperature.
2. Make sure that the inverter is installed according
to the manual and there is no shelter around the
inverter.
3. After the inverter is powered off and waiting for
30 minutes, then restart it. If the fault still exists,
please call the service center.
Check whether the actual battery voltage exceeds
the battery charging cut-off voltage by more than
20V.
Check whether the actual battery voltage is lower
than the battery discharge cut-off voltage.
Confirm that the wiring is normal, and check
whether the battery voltage sampling value is less
than 75V.
1. Try to lower the ambient temperature.
2. Make sure that the inverter is installed according
to the manual and there is no shelter around the
inverter.
3. After the inverter is powered off and waiting for
30 minutes, then restart it. If the fault still exists,
please call the service center.
1. Try to reduce battery power.
2. Restart the inverter to see if the fault still exists.
If it still exists, please call the service center.