6: Bell Circuits Device Type Input Registers - Honeywell CGW-MB Installation And User Manual

Som module
Table of Contents

Advertisement

Register Mapping
Table 7.24: Zones/Panel Circuits Holding Register Bit Definitions
Bit
14
15
No.
Ack
Bit
Prealarm
Block
Name
When individual upper byte bits are set to 1, the following definitions
apply:
Ack Block (Bit 15): All events on this bell circuit, other than fire alarm, are
acknowledged.
Prealarm (Bit 14): The bell circuit is in a prealarm state.
Trouble (Bit 13): The bell circuit is in a trouble state.
InActive (Bit 12): The bell circuit is not active.
Active (Bit 11): The bell circuit is active and there will be an active event
type in the lower byte.
Enable (Bit 10): The bell circuit is enabled.
Disable (Bit 9): The bell circuit is disabled.
Ack Fire Alarm (Bit 8): The fire alarm on this bell circuit is acknowledged.
The holding register address and the bell circuit contained in the address is detailed in
Table 7.25, "Bell Circuit Holding Register
7.21.6 Bell Circuits Device Type Input Registers
NOTE: If the point is not present in the panel programming, all bits in the byte will contain
a value of 1 or FFFFH.
Each bell circuits device type holding register address consists of two bytes as defined in
Table 7.26, "Bell Circuits Device Type Input Register Bit Definitions"
circuit as shown in
Bit
No.
CGW-MB Installation and Users' Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
Upper Byte
13
12
Trouble
InActive
Table 7.25: Bell Circuit Holding Register Addresses
Start Address
406001
406002
406003
406004
Table 7.27, "Bell Circuit Device Type -Input Register
Table 7.26: Bell Circuits Device Type Input Register Bit Definitions
Upper Byte
15
14
13
12
11
Device Types (see
Table 7.27: Bell Circuit Device Type -Input Register Addresses
Start Address
306001
306002
306003
306004
11
10
9
Active
Enable
Disable
Addresses".
End Address
406001
406002
406003
406004
10
9
8
7
6
7.30 "Device Types"
End Address
Device Address
306001
BellCircuit1
306002
BellCircuit2
306003
BellCircuit3
306004
BellCircuit4
Modbus Communications
Lower Byte
8
7
6
5
Ack
Fire
Alarm
Active Event Type (When
Bit 11 is set to 1, see
"CGW-MB Active Event
.)
Code"
Device Address
Bell Circuit 1
Bell Circuit 2
Bell Circuit 3
Bell Circuit 4
representing a bell
Addresses".
Lower Byte
5
4
3
2
)
4 3
2
1 0
7.29
1
0
64