Appendix A: CLSS Gateway mainboard Operating Conditions

Power Requirements
Working voltage range
Current
Location Requirements
Room Temperature
Operational Temperature
Relative humidity
CAUTION:THE USEFUL LIFE OF THE SYSTEM'S STANDBY BATTERIES AND THE
!
ELECTRONIC COMPONENTS MAYBE ADVERSELY AFFECTED BY EXTREME
TEMPERATURE RANGES AND HUMIDITY. THEREFORE, IT IS RECOMMENDED THAT
THIS SYSTEM AND ITS PERIPHERALS BE INSTALLED IN AN ENVIRONMENT WITH A
NORMAL ROOM TEMPERATURE OF 15 - 27° C (60 - 80° F).
A.1 Wirings and Power
NON-POWER LIMITED
POTS 1
POTS 2
CGW-MB Installation and Users' Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
Table A.1: Operational Requirements
18V - 30V DC
For HON-CGW-DACT: 180mA (maximum)
For CGW-MB: 140mA (maximum)
NOTE: The power requirement varies with the number of
interfaces used.
15 - 27° C (60 - 80° F)
0°C - 49°C (32°F - 120°F)
93% + 2% RH (Non-condensing) at 32°C + 2°C (90° F + 3°F)
J4
J5
POWER LIMITED