TEST INPUT

When a type 3 or type 4 safety device is not often actuated, it may be useful to test the connected emergency stop chain from
time to time. For this purpose, the FF-SRM200P2 muting module is equipped with a test output allowing to test the correct
functioning of the connected emergency stop chain (i.e. safety device incl. external contactors, safety control modules, etc.) at
certain steps of the process.
When connecting type 2 safety devices to the FF-SRM200P2 muting module, the test function must be used to check the safety
integrity of the safety device.
Safety devices compatible with the FF-SRM200P2 test output
FF-SLG18 and FF-SLG30 type 2 safety light curtains (all models with the exception of FF-SLG18147B2 and FF-SLG30147B2)
Safety switches (e.g. for safety door monitoring).
Modes with test (see table page 6)
Muting modes 50 to 79.
Mutual exclusion modes 92 and 93.
In these modes the output terminal 58 is used as test output and it must be connected to the test inputs of all connected safety
devices, that are tested simultaneously.
A test signal is generated
At each activation of the start push-button and each activation of the acknowledge push-button
At each new and valid muting sequence (muting lamp light on).
NOTICE
The FF-SLG18/30 emitter and receiver needs to be powered AFTER the FF-SRM200P2 muting module. Otherwise, the test
sequence at power up may not work.
The connected safety devices must respond within max. 200 ms after the generation of the test signal, otherwise the module
will display an error (see « Diagnostic Information »).
Specifications of the test output
Test output type (terminal 58)
Test active (voltage at terminal 58)
Test inactive (voltage at terminal 58)
Test output characteristics
Response time of safety device after generation of test signal
Test input example 1:
Muting using two FF-SLG18 / FF-SLG30 type 2 safety light curtains with test input (modes 50 to 69)
(dc+)
Fuse
1 A
0,5 A
1 A
max.
max.
2
3
6
(+)
Test
FF-SLG
FF-SLG
(-)
receiver
emitter
1
7 1
4
6
A1+
S11 S12 S14 S13
-
+ +
FF-SRM200P2
A2-
M1 M2 48
(dc-)
Note (A):
Connect test output terminal 58 to the test input of each FF-SLG18 / FF-SLG30 emitter as shown in the wiring diagram below while
respecting the polarity of the test input terminals (test input (+) = terminal 6, test input (-) = terminal 1).
Modes 50 to 59 (only): 1 non-mutable and 1 mutable safety device AND safety devices with test input: the mutable safety device
needs to be activated during the muting sequence.
107111-11-EN FR26 GLO 503 Printed in Germany
1 A
0,5 A
Fuse
max.
max.
1 A
2
3
Test
(A)
(A)
(+)
FF-SLG
FF-SLG
(-)
receiver
emitter
5
7 1
4
6
5
S21 S22 S24 S23
-
-
+ +
-
13 23
K3
Fuses
muting error /
6 A max.
restart
PNP static output, 24 Vdc, max. 100 mA
0 Vdc
+24 Vdc
Normally closed
Max. 200 ms
6
1
K3
SM1
SM2
K4
S31
S32
S34 S33
S41 S42 S44 S43
-
+ +
-
-
+ +
K1
K2
24 14
58
test output
machine
control
K4
(A)
Start
-
21