CGW-MB Control Features
7.19.2 Enabling the Control
CAUTION: UL LISTING
ENABLING CONTROL VOIDS THE UL LISTING OF THE CGW-MB.
CGW-MB control is enabled through a web page-based configuration tool running on the
CLSS Gateway mainboard. Enable control as follows:
1. Start the web browser on a computer that is in the same IP network as the CGW-
MB.
Note: Chrome is the recommended browser.
2. Enter the following URL in the browser:
https://192.168.10.190:9443/config/index.html
3. Do the following if any security warning is shown. Otherwise, go to step 4.
• Click the Advanced link below the error message.
• Agree to proceed.
4. In the CLSS Gateway mainboard Configuration Tool page, enter the password.
5. Go to Modbus Tools in Modbus Settings.
6. Enable or disable as needed in the control functionality.
7. Read the UL Void message shown, if it is enabled.
8. Click Save.
9. Wait until the CGW-MB shows the changes.
10.Check that the changes are correct.
7.19.3 Control Commands
Using the CGW-MB you can send relevant command values to the holding registers of
Points, Panels, and Zones.
NOTE: Refer to the

Point Commands

Serial
No.
1
EnableDisableDevice
2
EnableDisableDevice
Panel Commands
Serial
No.
CGW-MB Installation and Users' Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
Register Mapping
Command
0x400 - Enable
0x500 - Disable
Command
1
System Reset
2
Signal Silence
3
Deactivate Buzzer
4
Walk Test Sounder on
5
Walk Test no sounder on
6
Walk test off
section for detailed register mapping information.
Value
Use Device/Module Holding Register
Address
Use Device/Module Holding Register
Address
Lower Byte value
0x0000
0x0001
0xE
0xF
0x10
0x11
Modbus Communications
Holding Register
Holding
Register
20001
20001
20001
20001
20001
20001