Honeywell CGW-MB Installation And User Manual page 123

Som module
Table of Contents

Advertisement

BACnet PIC Statement
Standard Object Types Supported - Life Safety Point/Life Safety Zone
Present Value
Tracking
Value
Event State
Reliability
CGW-MB Installation and Users' Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
BACnet
Enumeration
LifeSafetyState
0
IssQuiet
1
IssPreAlarm
2
IssAlarm
3
IssFault
7
IssActive
22
IssSupervisory
BACnet
Enumeration
LifeSafetyState
0
IssQuiet
1
IssPreAlarm
2
IssAlarm
3
IssFault
7
IssActive
22
IssSupervisory
BACnet
BACnet Event
Enumeration
0
EsNormal
1
EsFault
2
EsOffNormal
BACnet
Enumeration
Reliability
0
reNoFaultDete
cted
7
re_UnreliableOt
her
BACnet
Normal
PreAlarm
Fire Alarm, Security Alarm
(Life/Property), Critical Process
Alarm, (Life/Property), Medical
Emergency, IB Smash Glass, Panic
Alarm
Security Trouble, Fire Trouble, Non-
Fire Trouble, Fire Device or Zone,
Disabled, Non-Fire Device Disabled
Non-Fire Activation
Supervisory (Equipment),
Supervisory (Guard's Tour)
BACnet
Normal
PreAlarm
Fire Alarm, Security Alarm
(Life/Property), Critical Process
Alarm (Life/Property), Medical
Emergency, IB Smash Glass, Panic
Alarm
Security Trouble, Fire Trouble, Non-
Fire Trouble, Fire Device or Zone,
Disabled, Non-Fire Device Disabled
Non-Fire Activation
Supervisory (Equipment),
Supervisory (Guard's Tour)
State
Normal
Security Trouble, Fire Trouble, Non-
Fire Trouble, Fire Device Disabled,
Non-Fire Device Disabled
All statuses other than normal and
fault.
BACnet
All statuses other than trouble.
Security Trouble, Fire Trouble, Non-
Fire Trouble
The BACnet Feature
Fire Panel State
Fire Panel State
Fire Panel State
Fire Panel State
122

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents