Bacnet Pic Statement; 1: Protocol Implementation Conformance Statement (Normative); Bacnet Protocol Revision: 14 - Honeywell CGW-MB Installation And User Manual

Som module
Table of Contents

Advertisement

BACnet PIC Statement

For the CGW-MB object addressing details, refer to the
CAUTION: THE NODE NUMBER OF THE CGW-MB SHOULD BE DIFFERENT FROM OTHER CLSS GATEWAY
!
MAINBOARDS IN THE NETWORK.
CAUTION: THE IP ADDRESS OF THE CGW-MB SHOULD BE DIFFERENT FROM OTHER CLSS GATEWAY
!
MAINBOARDS AND DEVICES IN THE NETWORK.
8.13 BACnet PIC Statement
8.13.1 Protocol Implementation Conformance Statement (Normative)

BACnet Protocol Revision: 14

Product Description
This product presents Fire Panel and Annunciator nodes (operating as part of a Fire Panel
network or stand-alone) and their associated objects as BACnet objects. Event
notification for Alarms, Troubles, and other states are sent to registered BACnet client
workstations. Control Functionalities supported for Gent – Silence/Unsilence, Reset and
Mute panels, Enable/Disable loop devices and Zones, Activate/De-activate Sounder and
LED.
BACnet Standardized Device Profile (Annex L):
BACnet Operator Workstation (B-OWS)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
BACnet Interoperability Building Blocks Supported (Annex K)
Data
Sharing
DS-RP-B
DS-RPM-B DM-DOB-B
DS-WP-B
DS-WPM-B (DM-RD-B)*
NOTE: DM-RD-B and AE-LS-B are supported for the Gent panels only.
Segmentation Capability
Segmented requests supported, Window Size 1024 Max
Segmented responses supported, Window Size 1024 Max
CGW-MB Installation and Users' Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
Device & Network
Management
DM-DDB-B
DM-LM-B
BACnet PIC Statement.
Alarm & Event
Scheduling
Management
AE-ACK-B
AE-ASUM-B
AE-N-I-B
AE-INFO-B
AE-LS-B*
The BACnet Feature
section.
Trending
121